PROBLEM 

POSSIBLE CAUSE 

ACTION 

Water not hot enough 

Coil inlet temperature too low 

 

 

 

Air lock(s) in engine cooling 

circuit 

 

Top of storage heater above 

engine cooling header tank 

 

Thermostat in engine cooling 

circuit not adjusted correctly 

 

Thermo-syphon in coil circuit 

when engine is not running 

Check coil inlet water 

temperature and correct if 

necessary 

 

Check for air locks 

 

 

Raise header tank 

 

 

Check setting on thermostat 

 

 

Contact your supplier for advice 

Water too hot 

Engine cooling circuit water too 

hot 

 

Immersion heater control 

thermostat set too high 

 

Immersion heater control 

thermostat has failed 

Fit thermostat CW276A or 

blender valve CW268 OR 

CW272B 

 

Adjust immersion heater control 

thermostat 

 

Check control thermostat. 

Do not reset high temperature 

cut-out until the cause of the 

overheating has been 

established 

Water discharges continuously 

through temperature/pressure 

relief valve 

Pump pressure switch cut-out 

setting is higher than relief valve 

setting. 

 

Pressure switch has failed 

 

Stored water too hot 

 

Immersion heater control 

thermostat set too high or has 

failed. 

 

Temperature/pressure relief 

valve has failed 

Check cut-out setting.  Adjust or 

replace switch, or fit pressure-

reducing valve 

 

Replace pressure switch 

 

Fit thermostat CW276A 

 

Adjust or replace control and 

high temp. thermostats 

 

 

Replace temperature/pressure 

relief valve 

Hot water flows back into cold 

water line 

Thermal expansion 

Fit non-return valve and 

expansion tank, as outlined in 

these instructions 

Immersion heater does not 

operate 

Electric supply failure 

 

Control thermostat temperature 

set too low. 

 

High temperature cut-out has 

operated 

Restore electric supply. 

 

Check control thermostat and 

correct if necessary. 

 

Check control thermostat and 

replace if necessary. 

Inspect system before using 

heater again. 

 

Check that high temperature 

cut-out setting is above control 

thermostat setting: reset at 90ºC 

 

PROBLEM SOLVING 

Содержание CWM141-V3

Страница 1: ...e best performance from your C Warm water storage heater please read these instructions carefully Failure to observe the recommended procedures may result in damage to equipment or in personal injury...

Страница 2: ...r 12 Regulating the temperature of engine heated stored water 14 Hot water expansion 15 Regulating the cold water inlet pressure 15 Using the heater 16 Maintenance 16 Winter precautions 16 Problem sol...

Страница 3: ...ine or with gas or diesel burners A mains voltage a c immersion heater can be fitted If an auxiliary burner is used follow the fitting and operating instructions supplied with it With water entering t...

Страница 4: ...s may be shortened Copper is moderately resistant to corrosion in hot sea water so the heater itself can be used with sea water though its working life may be shortened Because the temp pressure relie...

Страница 5: ...through the coil can be attained if required by taking off hot water from a point B downstream of A and returning it to point C upstream of D so that the pressure difference between the coil take off...

Страница 6: ...e storage heater can be located above or below engine level For best circulation natural convection should assist the pumped flow II There must be no air locks in the cooling water circuit Either loca...

Страница 7: ...e heater coil Connect it to the overflow outlet on the original header tank using a suitable pressure hose see diagram The expansion tank for a car radiator is suitable for engine cooling systems up t...

Страница 8: ...ill depend on the construction of the vessel and on the available space Some suggested installation methods are indicated below VERTICAL MODELS 1 litre of water weighs 1 kg Locate the heater on a firm...

Страница 9: ...ains 2 webbing straps 4 stainless steel brackets Instructions for use or Use Either a C Warm Strap Kit or a C Warm Bracket Kit H series can be used to secure the heater in place Leave space under the...

Страница 10: ...connections suitable adapters and compression fittings should be used These may be obtained from a plumber s merchant or from most Do it Yourself stores See pages 18 20 for connection sizes The pipew...

Страница 11: ...the valve must point downwards with a suitable hose to allow hot water or steam to escape safely to the bilge or another suitable area The relief valve supplied with the heater is non adjustable and...

Страница 12: ...sion heater when the water temperature reaches 90 C Thermostat Settings The control thermostat on the immersion heater is pre set to cut out when the water temperature reaches 60 C This is ample for d...

Страница 13: ...N HEATER OBTAIN THE SERVICES OF A QUALIFIED ELECTRICIAN Wiring diagram for a Cleghorn Waring double protected Immersion Heater Model Number CW279 2kW Voltage 220 240 v a c Recommended fuse 10 amp Mode...

Страница 14: ...hot water supply by l fitting a C Warm adjustable thermostat model CW276A This also avoids the possibility of tripping the high temperature cut out in a C Warm double protected electric immersion heat...

Страница 15: ...ason REGULATING THE COLD WATER INLET PRESSURE Where the cut out pressure of the pressure system pump exceeds or is close to the pressure of the temperature and pressure relief valve TPRV a PRESSURE RE...

Страница 16: ...check all the connections once more when the water is heated for the first time 4 Your pressurised system and C Warm heater are now ready for use 5 Your engine cooling circuit will heat the stored fre...

Страница 17: ...usly through temperature pressure relief valve Pump pressure switch cut out setting is higher than relief valve setting Pressure switch has failed Stored water too hot Immersion heater control thermos...

Страница 18: ...ext int ext ext ext ext int CWM18 H3 18 2 CWM21 V3 20 int int 2 CWM29 V3 29 2 CWM29 VT3 29 2 CWM32 H3 32 2 CWM40 V3 40 int int 2 CWM41 H3 40 int int 2 CWM41 HT3 40 int int 2 CWM45 H3 45 2 CWM50 V3 50...

Страница 19: ...19 See Table page 18 NOT TO SCALE HORIZONTAL MODELS...

Страница 20: ...20 See Table page 18 NOT TO SCALE VERTICAL MODELS...

Страница 21: ...rts returned to us under a warranty claim shall be the responsibility of and at the expense of the claimant x we accept no responsibility for loss or damage howsoever occasioned to customers goods whi...

Отзывы: