LED status
Error
Cause
Remedy
E03
The supply voltage is
too high.
1. Check that the grid voltage is in accordance with the
rated values.
2. Reset the error.
3. If the problem continues, replace the pump.
E03 or E06
The regeneration
effect occurs because
the other equipment
generates the water
flow.
1. Remove the source of the flow.
2. Reset the error.
3. If the problem continues, replace the pump.
E04
• The motor is
stalled.
• The rotor is
blocked or loss of
speed.
1. The unit automatically carries out several high-torque
startup attempts.
2. If the problem continues, do the following methods:
– Check that the pumped liquid is in accordance
with the working limits.
– Clean the system.
– Reset the error.
23.
3. If the problem continues, replace the pump.
E05
The motor control
shows error.
1. Reset the error.
2. If the problem continues, replace the pump.
E06
The supply voltage is
too low.
1. Check that the grid voltage is in accordance with the
rated values.
2. Reset the error.
3. If the problem continues, replace the pump.
E07
The motor is overload. 1. Reset the error.
2. Check that the pumped liquid is in accordance with the
working limits.
3. If the problem continues, replace the pump.
E08
The motor gets
overheated.
1. Reset the error.
2. Check that the ambient and pumped liquid
temperature is in accordance with the working limits.
3. Check that the unit is installed according to the
instructions in the manual.
4. If the problem continues, replace the pump.
E09
The electrical motor
fails.
1. Reset the error.
2. If the problem continues, replace the pump.