![Xylem Bell & Gossett 15GDS Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/xylem/bell-and-gossett-15gds/bell-and-gossett-15gds_instruction-manual_3969272012.webp)
10
15GDS/20GDS Installation, Operation and Maintenance Manual
The motors are tested in accordance with IEC 34-1, 1969.
The stator is insulated in accordance with class F (310º F, 155º C). The motor is designed
to deliver its rated output at ± 5% variation from the rated voltage. Without overheating
the motor, ± 10% variation from the rated voltage can be accepted provided that the
motor does not run continuously at full load. The motor is designed to operate at a
voltage imbalance of up to 2% between the phases.
Monitoring Equipment
The stator incorporates thermal contacts connected in series.
The pump can be equipped with sensors for sensing water in the stator housing.
General Design of a 15GDS/20GDS Pump (continued)