Xtreme C60-800 Скачать руководство пользователя страница 5

Xtreme Power Conversion Corporation

C60 User’s Manual

Page 5

Uninterruptible Power Supply

Indicators & Alarm Conditions

Condition

Visual Indicator

Alarm

AC mode

Green LED illuminated

No Audible Alarm

Battery mode

Green LED flashes every 10 seconds

Audible Alarm sounds every 10 

seconds

Low battery mode

Green LED flashes every 1 second

Audible Alarm sounds every 1 

second

Fault

Red LED is illuminated

Audible Alarm is continuous

Overload

Audible Alarm sounds every 0.5 

seconds

IMPORTANT SAFETY INSTRUCTIONS: (SAVE THESE INSTRUCTIONS)

CAUTION! (UPS having Internal Batteries): 

Risk of electrical shock – Hazardous live parts inside this unit are ener‐

gized from the battery supply even when the input AC power is disconnected.

CAUTION! (No User serviceable Parts): 

Risk of electrical shock, do not remove cover. No user serviceable parts 

inside. Refer servicing to qualified service personnel.

CAUTION! (Non‐isolated Battery supply): 

Risk of electric shock, battery circuit is not isolated from AC input, haz‐

ardous voltage may exist between battery terminals and ground. Test before touching.

WARNING!

 Unit intended for installation in a controlled environment.

CAUTION! 

Do not dispose of batteries in a fire, the battery may explode.

 

CAUTION! 

Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.

CAUTION! 

A battery can present a risk of electric shock and high short circuit current. The following precaution 

should be observed when working on batteries:

Remove watches, rings or other metal objects.

Use tools with insulated handles.

To reduce the risk of electric shock, disconnect the UPS from the main supply before installing a computer inter‐

face signal cable. Reconnect the power cord only after signaling interconnections have been made. Servicing of 

batteries should be performed or supervised by personnel with knowledge of batteries and the required precau‐

tions. Keep unauthorized personnel away from batteries.

The instructions contained within this safety manual are deemed important and should be closely followed at all 

times during installation and follow‐up maintenance of the UPS and batteries.

  CAUTION: 

The unit has a dangerous amount of voltage. If the UPS indicator is on, the unit’s outlets may have 

a dangerous amount of voltage even when not plugged into the wall outlet because the battery may continue to 

supply power. Care should be taken to undertake installation indoors, free from electrically‐conductive particles 

which are under temperature and humidity control, in order to reduce the risk of electric shock. It is best to dis‐

connect the device using the power supply cord. Ensure that the equipment is placed in a position near the outlet 

where easily accessible. All servicing on this equipment must be carried out by qualified service personnel. Before 

conducting any maintenance, repair, or shipment, first ensure that everything is turned off completely and discon‐

nected.

Содержание C60-800

Страница 1: ...60 Standby UPS 800VA Models User Installation Manual 2015 Xtreme Power Conversion Corporation All rights reserved Rev 6 23 15 For more information visit www 247technology com on line ups c60 standby ups ...

Страница 2: ...ninterruptible Power Supply Table of Contents Package Contents 3 ProductIntroduction 3 Product Overview 3 Installation Initial Startup 4 Indicators Alarm Conditions 5 Troubleshooting 6 Specifications 7 Obtaining Service 8 Xtreme Power Conversion Limited Warranty 9 ...

Страница 3: ... set up your system for the maximum safety and performance Included is information on customer support and service if it is required If you experience a problem with the UPS please refer to the Troubleshooting section in this manual to correct the problem If the problem is not corrected please collect in formation so that the Technical Support personnel can more effectively assist you Product Over...

Страница 4: ... on the front of the UPS For best results the batteries in the UPS should be charged for at least 8 hours before use The UPS charges its battery while it is connected to AC utility power and powered on Connecting the Loads Plug the loads to be supported by the UPS into the output receptacles on the rear of the UPS Simply turn the power switch on the UPS on and the devices connected to the UPS will...

Страница 5: ...ric shock and high short circuit current The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles To reduce the risk of electric shock disconnect the UPS from the main supply before installing a computer inter face signal cable Reconnect the power cord only after signaling interconnections have been made Serv...

Страница 6: ...d Remove some of the load from the output of the UPS UPS fault Return the unit for service Alarm sounds every 2 seconds when the AC input is normal Battery defect Replace the battery with the same type of battery Charging circuit is damaged Return the unit for service When power fails backup time is shorter than expected The UPS is overloaded Remove some of the load from the output of the UPS Batt...

Страница 7: ...ated sine wave battery mode Transfer time 2 6 ms Outlets 2 NEMA 5 15R 2 IEC C13 Overload capacity 110 20 10 for 5 min 120 20 10 immediately off Efficiency 95 BATTERY UPS battery type 1 12V 9AH 12VDC UPS charge current 1A maximum Recharge time 8 hours to 90 capacity PHYSICAL Dimensions W x D x H 4 0 x 13 0 x 5 7 in Weight 7 5 lbs ENVIRONMENT Temperature 32 104 F 0 40 C Humidity 0 90 Altitude 11 500...

Страница 8: ...sk you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the ...

Страница 9: ...PC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written instructions Any technical advice furnished b...

Отзывы: