Xtreme Power Conversion XPRT Series Скачать руководство пользователя страница 2

Date: 2007-05-18 

Page: 2 of 11 

Version 1.1 

Safety Warning and Caution! 

 

1.  Risk of Electric Shock, This Battery Pack contains batteries inside, Energized 

parts and Hazardous electrolyte are harmful to personnel. Hazardous voltage 
may exist between battery terminals and ground. Test before touching. 

2.  This Battery Pack is designed for installation in a controlled environment. To 

reduce the risk of fire, replace only with the same type and rating of fuse or 
circuit breaker. 

3. 

Warning, Battery Pack is very heavy. Please be very careful when handling and 
installing the Battery pack. Do not install the battery pack by the two front 
mounting ears only. The adjustable rack rails( Model #: XPRT-RR1) illustrated 
in this manual are required for installtion 

4.  Do not dispose of batteries in a fire. The battery may explode. 
5.  There is No user serviceable parts inside the enclosure. Do not open or mutilate 

the batteries, released electrolyte is harmful to the skin and eyes. It may be toxic. 
Servicing of batteries should be performed or supervised by personnel with 
knowledge of batteries and the required precautions.   

6.  A battery can present a risk of electric shock and high short circuit current. The 

following precaution should be observed when working with batteries: 

---  Remove watches, rings or other metal objects. 
---  Use tools with insulated handles. 
---  Wear rubber gloves and boots. 
---  Do not lay tools or metal parts on top of batteries. 
---  Disconnect charging source prior to connecting or disconnecting battery 

terminals. 

 

Specifications for Battery Pack 

Model XPRT-BP1 

XPRT-BP2 

XPRT-BP3 

Battery type 

Lead-acid 

  7 Ah /12 V 

Lead-acid 

  7 Ah /12 V 

Lead-acid 

  7 Ah /12 V 

Number of batteries 

12 

12 

DC Bus Voltage 

36Vdc 

36Vdc 

72Vdc 

Dimensions W x D x H mm 

428 x 425 x 84 

428 x 610 x 84 

428 x 610 x 84 

Weight    (Kg / lbs) 

22 / 49 

44 / 96 

44 / 96 

 

Содержание XPRT Series

Страница 1: ...Date 2007 05 18 Page 1 of 11 Version 1 1 Instruction Manual For Battery Pack Installation Xtreme Performance Rack Tower Series XPRT ...

Страница 2: ... explode 5 There is No user serviceable parts inside the enclosure Do not open or mutilate the batteries released electrolyte is harmful to the skin and eyes It may be toxic Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and the required precautions 6 A battery can present a risk of electric shock and high short circuit current The following preca...

Страница 3: ...Date 2007 05 18 Page 3 of 11 Version 1 1 Battery Pack Installation Instructions 1 Installing the left Slide Rail on to the Post of Rack 2 Installing the right Slide Rail on to the Post of Rack ...

Страница 4: ...Date 2007 05 18 Page 4 of 11 Version 1 1 3 Placing the Battery Pack on to the Slide Rails 4 Fastening the left Bracket 5 Fastening the right Bracket ...

Страница 5: ...e 2007 05 18 Page 5 of 11 Version 1 1 6 Slide the Battery Pack into position and using the screws to fasten the Brackets to the Front Posts of The Rack 7 Top View of the installed Battery Pack on the Rack ...

Страница 6: ...Date 2007 05 18 Page 6 of 11 Version 1 1 8 The Close up View of the Bracket on the Rack Post ...

Страница 7: ...ar Panel of External Battery Pack and on Rear Panel of UPS z Use the battery cable provided with the External Battery Cabinet to connect the External Battery Pack to the UPS Unit z If More than one Battery Pack are to be connected then Connect the second Battery Pack to the first one with the Battery Cable provided with the second Battery Pack z Please check and set UPS parameters to match the Bat...

Страница 8: ...Date 2007 05 18 Page 8 of 11 Version 1 1 Rear Panel View of 700VA 1500VA UPS and EBP 12 pcs Batteries ...

Страница 9: ...Date 2007 05 18 Page 9 of 11 Version 1 1 Rear Panel View of 2000VA 3000 VA UPS EBP 12 pcs Batteries 1 Make sure the Breaker on Battery Pack is in OFF Position ...

Страница 10: ... 1 10 Connect the Electrical Connections between UPS and Battery Pack The EBP Connector is keyed so as to insure correct Polarity 11 Then Turn the Breaker on Battery Pack to On Position Obtaining Service Warranty If the UPS requires Service ...

Страница 11: ...or the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Material Authorization Number RMA G If the UPS is under warranty the repairs will be done at no charge If not there will be a charge for repair 4 Pack the UPS in its original packaging If the original packaging is no longer avail...

Страница 12: ...ations Life Support Disclaimer Xtreme Power power protection products are not designed intended or authorized for use in systems intended to support or sustain life or for any other application in which the failure of the Xtreme Power product could create a situation where personal injury or death may occur Under no circumstances should the Buyer purchase or use Xtreme Power products for any such ...