background image

P91 Lead Acid 2U User

s Manual 

Uninterruptible Power Supply 

Xtreme Power Conversion Corporation

 

Page 34 

 

 

 

 

3.     

XPC  will  evaluate  the  Product  to  determine  its  level  of  functionality,  and  will  examine  the  Product  for 

evidence of damage from a Power Disturbance.

 

•   

If  XPCs'  evaluation  provides  no  evidence  of  damage  from  a  Power  Disturbance,  XPC  will  send  to  the

 

Purchaser (i) a report summarizing the tests performed and (ii) a rejection of claim notice.

 

• 

If the Product shows evidence of damage from a Power Disturbance, XPC will request that all Connected 

Equipment  for  which  a  Load  Protection  Policy  claim  has  been  submitted,  be  sent  for  evaluation  to 

either XPC or an authorized service center. If it is determined that the Connected Equipment has been 

damaged  by  a Power  Disturbance,  XPC  will,  in  its  sole  discretion,  issue  payment to  the  Purchaser  for 

either  the  cost  of  repair  of  the  Connected  Equipment      or      the  Fair  Market  Value  of  the  damaged 

Connected  Equipment,  up  to  the  dollar  limits  stated  above.      XPC  reserves  the  right  to  require  the 

Purchaser to transfer title and deliver the Connected Equipment to XPC if it chooses to reimburse the 

Purchaser for the  fair market value  of the  Connected Equipment.       XPCs' maximum  liability  shall be 

reduced to reflect all such other payments or sources of recovery, whether applied for or not.

 

4.     

If XPC issues payment to the Purchaser to have the Connected Equipment repaired, the repair must be

 

performed  at  a  service  center  that  is  authorized  by  the  manufacturer  of  the  Connected  Equipment.  XPC 

reserves the  right to  contact  the authorized service  center  directly  to  discuss  repair  costs  and damage to the 

Connected Equipment to determine if it was caused by a Power Disturbance and the right to request that the 

service  center  forward  the  Connected  Equipment  or  components  of  the  Connected  Equipment  to  XPC  for 

inspection

 

5.     

Unless modified in writing signed by an officer of XPC and the Purchaser, the terms of this policy are the

 

complete and exclusive agreement between the parties, superseding all prior agreements, oral or written, and 

all other communications between the parties relating to the subject matter of this agreement. No employee 

of  XPC  or  any  other  party  is  authorized  to  make  any  representations  beyond  those  made  in  this  agreement 

concerning the Load Protection Policy.

 

 

 

XPC Corporation

 

230 Yuma Street

 

Denver, CO 80223

 

1.800.582.4524

 

Содержание P91g Series

Страница 1: ...P91 P91g Lead Acid Online UPS 1000VA 2000VA 3000VA Models User Installation Manual www xpcc com 2021 Xtreme Power Conversion Corporation All rights reserved Rev 10 21 21...

Страница 2: ...Setup the UPS 7 2 5 Battery Replacement 11 2 6 Battery Kit Assembly 12 3 Operations 15 3 1 Button operation 15 3 2 LCD Panel 15 3 3 Audible Alarm 16 3 4 LCD display wordings index 17 3 5 UPS Setting...

Страница 3: ...Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no pr...

Страница 4: ...ify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors To avoid electrical shock turn off the unit and unplug it form the A...

Страница 5: ...to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment i...

Страница 6: ...ure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view P91g models 1500 Model 2000 Model 3000 Model P91 models 1000 1500 Mod...

Страница 7: ...ptible Power Supply Xtreme Power Conversion Corporation Page 5 5 USB communication port 6 RS 232 communication port 7 SNMP intelligent slot 8 Emergency power off function connector EPO 9 External batt...

Страница 8: ...Rectifier PFC Dynamic Bypass Inverter Battery Charger The UPS is composed of mains input EMI RFI filters rectifier PFC inverter battery charger DC to DC converter battery dynamic bypass and UPS output...

Страница 9: ...clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Place UPS It s equipped with fan for cooling Therefore place the UPS in a well ventilated area It s required to mainta...

Страница 10: ...ttery pack s Note If you have multiple battery packs available connect them serially An example is shown in the diagram below connecting the second battery connector of the first battery pack to the f...

Страница 11: ...onnection There are two kinds of outputs programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During pow...

Страница 12: ...able EPO function This UPS is equipped with EPO function By default the UPS is delivered from factory with Pin 1 and pin 2 closed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation...

Страница 13: ...er restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is...

Страница 14: ...connect the battery wires Put the front panel back to the unit 2 6 Battery Kit Assembly NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit p...

Страница 15: ...embled battery packs on one side of plastic shells as below chart Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit Step 1 Remove adhesive tap...

Страница 16: ...ation Page 14 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Tapes Tapes Step 3 Put assembled battery packs on one side of plastic shells Step...

Страница 17: ...g this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input freq...

Страница 18: ...frequency load current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overl...

Страница 19: ...ngs index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shut...

Страница 20: ...Vac For P91 models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output vol...

Страница 21: ...ting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For P91 models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable di...

Страница 22: ...els 55 59Hz setting the frequency low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Progra...

Страница 23: ...ty as following table for reference Battery capacity AH Total charging current A 7 20 2 20 40 4 40 60 6 60 8 14 Charger boost voltage setting Interface Setting Parameter 2 Set up the charger boost vol...

Страница 24: ...ing mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery in online mode E...

Страница 25: ...4 x Over input current 49 x 3 8 Warning indicator Warning Icon flashing Code Alarm Low Battery Sounding every 2 seconds Overload Sounding every second Over input current Sounding 2 beep every 10 secon...

Страница 26: ...ttery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Страница 27: ...r at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 2A on LCD display and al...

Страница 28: ...are horizontal brackets tower pedestals user manual AVAILABLE OPTIONS Bypass distribution XBDM power distribution XPDU 4 post rail kit 2 post shelf kit wall mount bracket Depending on load level P91g...

Страница 29: ...930W 16A 125Vac input 2000VA 1850W 16 7A 120Vac input 2000VA 1740W 17 4A 115Vac input 2000VA 1640W 18 2A 110Vac input 1800VA 1500W 18A 100Vac input P91 3000 100 125Vac 50 60Hz 24A 1 100 110 115 120 12...

Страница 30: ...P90 BP72 Used with UPS Models P91 1500 P91g 1500 P91 2000 P91g 2000 P91 3000 P91g 3000 Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Battery Numbers 6 12 8 12 Dimensions WxDxH 17 2 x 18 9 x 3 5 in 17...

Страница 31: ...echnician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mater...

Страница 32: ...the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjecte...

Страница 33: ...r d the total amount of all payment s you have or are entitled to receive from insurance other warranties extended warranties a legal liability claim or from other sources or persons for the damaged C...

Страница 34: ...vice may be connected to the output sockets of the Product The installation must comply with all applicable electrical and safety codes set forth pursuant to the NEC 4 The Product must have undeniable...

Страница 35: ...ILITY OF SUCH DAMAGE SUCH DAMAGES INCLUDE BUT ARE NOT LIMITED TO LOSS OF PROFITS LOSS OF SAVINGS OR REVENUE LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR ANY ASSOCIATED EQUIPMENT LOSS OF SO...

Страница 36: ...nt to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum liability shall be reduced to reflect all such other payments or sources of recover...

Отзывы: