XCC Product Guide
Xtralis Pty Ltd
28
www.xtralis.com
7.3
Default Settings
Table 7-2: Default values for the XCC detector
Parameter
Default
Value
Range
Minimum
Access
Minimum
Maximum
Fire-Alarm Threshold
Level I
Level I
(highest
sensitivity,
lowest
threshold)
Level IV
(lowest
sensitivity,
highest
threshold)
Adm
Simultaneous Alarm
Delays
10 Seconds
0 Seconds
60 Seconds
Adm
Air flow Thresholds
Normal
Normal
Wide
Faults Latched
Latched
n/a
n/a
Adm
Filter Service Interval
1825 days (5
years)
1 day
(Dependent
on
environment)
1825 days (5
years)
Adm
7.4
Spare Parts
On larger sites having multiple detectors it is advisable to stock certain critical spare parts. A list of spare
parts with quantities required is given below:
Table 7-3: Recommended spare parts stock
Part No.
Description
Number of detectors Installed to warrant ONE
Spare Part
Normal Service
Mission Critical
VSP-005
Filter Cartridge
50
20
VSP-501
Aspirator
n/a
20
Содержание XCC-010
Страница 1: ...Xtralis Class C XCC Product Guide XCC 010 XCC 01000 MRN May 2011 D N 14159_07 P N 29185 ...
Страница 2: ......
Страница 6: ...XCC Product Guide Xtralis Pty Ltd iv www xtralis com This page is intentionally left blank ...
Страница 8: ...XCC Product Guide Xtralis Pty Ltd 2 www xtralis com This page is intentionally left blank ...
Страница 14: ...XCC Product Guide Xtralis Pty Ltd 8 www xtralis com This page is intentionally left blank ...
Страница 24: ...XCC Product Guide Xtralis Pty Ltd 18 www xtralis com This page is intentionally left blank ...
Страница 26: ...XCC Product Guide Xtralis Pty Ltd 20 www xtralis com This page is intentionally left blank ...
Страница 33: ...Xtralis Pty Ltd XCC Product Guide www xtralis com 27 Figure 7 2 XCC detector dimensions rear view ...