![Xtralis XAS-1-US Скачать руководство пользователя страница 45](http://html.mh-extra.com/html/xtralis/xas-1-us/xas-1-us_product-manual_890684045.webp)
5
Testing
Note:
Testing should only be carried out by qualified personnel. To prevent unwanted alarms, ensure that the
proper authorities have been informed and that the unit has been isolated from the fire alarm system.
Note:
In cases where the control panel provides an alarm test facility, this may be used in place of the following
alarm tests.
5.1
Point Detectors
Open Area Application Testing
l
With the unit powered up and top cover removed the detectors can be tested for alarm functionality using
methods described by the manufacturer (for example, aerosol spray).
l
An airflow test may also be performed at this time as the detector should report a low flow fault with the top
cover removed.
Duct Application Testing
1. Unplug the test port plug (A).
2. Spray 3 to 5 second bursts of smoke from the aerosol smoke tester.
3. The point detector must go into alarm within 10 seconds. If the detector fails to go into alarm, perform
troubleshooting. Refer to Chapter 7 for further information.
4. Insert the rubber plug back into the test port hole to avoid an airflow fault.
A
B
Figure 5-1: Smoke Test Port
5.2
System
The installed system must be checked with the top cover securely fitted.
For open area applications, smoke should be introduced to the furthest sampling point from the XAS-1-US system
on each branch of the pipe.
The choice of smoke source is dependant on the installation but in all cases the smoke must be present for the
duration of the test - some aerosol sprays for point detectors may not work on aspirated systems. Manufacturers
recommended test method(s) for the specific detector mounted in the XAS-1-US should be followed.
If it is possible to get close to the sampling point then a basic "Go / No-Go" functional test can be carried out with
smoke matches or lighted paper etc.
Xtralis Pty Ltd
Xtralis XAS-1-US Product Guide
www.xtralis.com
37
Содержание XAS-1-US
Страница 1: ...Xtralis XAS 1 US Product Guide October 2016 Document 20635_08 Part Number 29875 ...
Страница 2: ......
Страница 10: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 2 www xtralis com This page is intentionally left blank ...
Страница 12: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 4 www xtralis com This page is intentionally left blank ...
Страница 24: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 16 www xtralis com This page is intentionally left blank ...
Страница 40: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 32 www xtralis com This page is intentionally left blank ...
Страница 48: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd Figure 6 1 Air Inlet Filter Removal 40 www xtralis com ...
Страница 50: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 42 www xtralis com This page is intentionally left blank ...
Страница 52: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 44 www xtralis com This page is intentionally left blank ...