![Xtralis XAS-1-US Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/xtralis/xas-1-us/xas-1-us_product-manual_890684019.webp)
2.3
Point Detectors
The supported point detectors have successfully passed required tests to allow use within the XAS-1-US product
and application. Refer to Chapter 3 on page 17 for further details of how dilution affects detector sensitivity.
If the installation is to be done in accordance with NFPA 72 requirements, then the detector must have been tested
for use in the system. Please refer to the list of approved detectors in Section 2.3.1.
2.3.1
Point Detector Selection
The following detectors have been listed for use in the XAS-1-US unit and are suitable for installations requiring a UL
Listing. The table shows the limits that should not be exceeded if the installation is to conform to requirements. All
figures are based on the following configurations:
l
Meets standard pipe configurations shown in Section "Open Area Applications" on page 21
l
Fan speed of 9 unless otherwise stated
l
Low fault threshold = 4
l
High fault threshold = 8
l
Flexible tube ID = 1/2 in (12.7 mm)
Detector
Sensitivity
Air Velocity Range(s)
Open Area Holes per Pipe
Apollo Series 65 models:
l
55000-325
l
55000-326
l
55000-327
1.00 %/ft – 1.4 %/ft
Open Area
0 – 300 FPM
Duct
0 – 2000 FPM
l
1 hole, 5/16"
l
2 holes, 13/64"
Apollo XP95 Analog model:
l
55000-650
1.30 %/ft – 3.43 %/ft
Open Area
0 – 300 FPM
Duct
0 – 4000 FPM
l
1 hole, 5/16"
l
2 holes, 13/64"
Hochiki Analog ALK-V
(UL)
1.00 %/ft - 2.06 %/ft
Open Area
0 – 300 FPM
Duct
l
0 - 2000 FPM – 1.00 %/ft – 2.06 %/ft
l
2000 – 3000 FPM – 1.0 %/ft – 1.5 %/ft
l
3000 – 4000 FPM – 1.0 %/ft
l
1 hole, 5/16"
l
2 holes, 13/64"
Hochiki SLV-24V
(UL)
1.63 %/ft
Open Area
0 – 300 FPM
Duct
0 – 4000 FPM
l
1 hole, 5/16"
Hochiki SLV-24V
(ULC)
1.93 %/ft
Open Area
0 – 300 FPM
l
1 hole, 5/16"
Hochiki Analog ALN-V(H)
(UL)
2.41 %/ft – 3.09%/ft
Open Area
0 – 300 FPM 2.41 %/ft
Duct
0 – 4000 FPM 3.09 %/ft
l
1 hole, 5/16"
Hochiki Analog ALN-V(H)
(ULC)
1.87 %/ft
Open Area
0 – 300 FPM
l
1 hole, 5/16"
Table 2-1: Tested and Certified Detectors
Xtralis Pty Ltd
Xtralis XAS-1-US Product Guide
www.xtralis.com
11
Содержание XAS-1-US
Страница 1: ...Xtralis XAS 1 US Product Guide October 2016 Document 20635_08 Part Number 29875 ...
Страница 2: ......
Страница 10: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 2 www xtralis com This page is intentionally left blank ...
Страница 12: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 4 www xtralis com This page is intentionally left blank ...
Страница 24: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 16 www xtralis com This page is intentionally left blank ...
Страница 40: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 32 www xtralis com This page is intentionally left blank ...
Страница 48: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd Figure 6 1 Air Inlet Filter Removal 40 www xtralis com ...
Страница 50: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 42 www xtralis com This page is intentionally left blank ...
Страница 52: ...Xtralis XAS 1 US Product Guide Xtralis Pty Ltd 44 www xtralis com This page is intentionally left blank ...