XTRALIS VESDA LASER INDUSTRIAL (VLI) – QUICK SETUP TECHNICAL GUIDE 

 

For internal use only                                                 Authored by: Manuel Espaillat 

 

How to clear fault 322 on VLI-880 or VLI-885 

How to clear fault 322 on VLI-885 

Refrain using Mains OK for VESDAnet GPI, change it to Reset or other function as above. If power supply monitoring is required, 
use the Detector GPI. Ensure that Detector GPI is connected in such a way that voltage > 5V appears on its terminals for GPI 
activation. 

How to clear fault 322 on VLI-880 

If fault 322 is reported after VSC connection, follow this procedure. 

Double click on VESDA VLI on left and go to the General tab, under IFC1 Name select VESDAnet card 

 

You will get following warning, press OK

 

 

 

You will get following screen, press OK 

AUTHORISED DISTRIBUTOR OF VESDA 

www.flamestop.com.au | [email protected]

Содержание VESDA VLI

Страница 1: ...ia a standard local Type B USB port This type of USB cable is most commonly used with USB printers The connector that plugs into the computer is known as Type A The USB cable is NOT included with the...

Страница 2: ...ferential where the exhaust pipe needs to go back to the sampling area keep the exhaust pipe length at a minimum Connect the VLI to the installed pipe network select relevant pipes in use through VSC...

Страница 3: ...he list of available detectors then select Next 9 Enter a unique name for the device then select Finish 10 Go to the Connection menu and select Open Connection and view next the Bacnet USB connection...

Страница 4: ...monitoring is required use the Detector GPI Ensure that Detector GPI is connected in such a way that voltage 5V appears on its terminals for GPI activation How to clear fault 322 on VLI 880 If fault...

Страница 5: ...UIDE For internal use only Authored by Manuel Espaillat 5 Double click again on VESDA VLI on left and select Input outputs you will get following warning Press OK you will get the following screen AUT...

Страница 6: ...nternal use only Authored by Manuel Espaillat 6 Change VESDAnet Card GPI to Reset as shown below Press OK double click VEASDA VLI on left again will get following screen and then select Empty under IF...

Страница 7: ...SER INDUSTRIAL VLI QUICK SETUP TECHNICAL GUIDE For internal use only Authored by Manuel Espaillat 7 Then press OK then reset detector fault 322 will clear AUTHORISED DISTRIBUTOR OF VESDA www flamestop...

Отзывы: