XTRALIS VESDA LASER INDUSTRIAL (VLI) – QUICK SETUP TECHNICAL GUIDE
For internal use only Authored by: Manuel Espaillat
4
How to clear fault 322 on VLI-880 or VLI-885
How to clear fault 322 on VLI-885
Refrain using Mains OK for VESDAnet GPI, change it to Reset or other function as above. If power supply monitoring is required,
use the Detector GPI. Ensure that Detector GPI is connected in such a way that voltage > 5V appears on its terminals for GPI
activation.
How to clear fault 322 on VLI-880
If fault 322 is reported after VSC connection, follow this procedure.
Double click on VESDA VLI on left and go to the General tab, under IFC1 Name select VESDAnet card
You will get following warning, press OK
You will get following screen, press OK