XTRALIS VESDA LASER INDUSTRIAL (VLI) – QUICK SETUP TECHNICAL GUIDE 

 

For internal use only                                                 Authored by: Manuel Espaillat 

 

Startup 

 

Let the detector run for around 15 minutes ensuring that the pipe flow rates are within the required minimum 
(25+ ltr/min per pipe or 50+ ltr/min for whole detector) , ignore the faults but reset the detector at 15 minutes 
after the power-up. 

 

Normalize the flows, it takes around 10 more minutes, the pipe flow rates should be close to the Aspire II 
predictions. 

 

Reset the detector after normalization and it should be running without the faults if the flow rates are 
maintained as the acceptable minimums (25+ ltr/min per pipe or 50+ ltr/min for whole detector). 

Connecting to the Detector 
 

Xtralis VSC supports connecting to a VLI detector via a range of connection mechanisms and 
communication protocols. Connection methods are defined and saved for future use within the 
Connection Manager. 
 
To define a connection to a standalone VLI detector, follow this procedure: 

 

Creating a USB Connection 

1.  Open the VLI detector and connect the USB cable from the USB socket on the main board of the VLI to a 

PC or laptop located near the detector with the Xtralis VSC software installed. 

2.  Select 

Connection | Manager 

from the menu system. The Connection Manager dialog is displayed. 

3.  Select 

Add

. The Add Connection dialog is displayed. 

4.  Select the BACnet connection option, then select 

Next

5.  Select BACnet from the Add Connection dialog box 
6.  Select USB, then select Next 
7.  Enter a unique BACnet Device ID, then select Next. 
8.  Select the detector type from the list of available detectors, then select Next. 
9.  Enter a unique name for the device, then select Finish. 
10.  Go to the 

Connection

 menu and select 

Open Connection and view

, next the 

Bacnet USB

 connection 

dialog box will appear, click 

OK

 

Troubleshooting 

 (Note: It is normal for a new system to indicate airflow faults. These are rectified as part of the setup and 
commissioning process), VLI may report new fault codes that most installers/technicians may not be familiar with. 
New detector firmware and future VSC releases will resolve these troubles. Below are some of the most commonly 
reported faults by VLI and their known solutions: 

Fault 311

 – Absolute flow for whole detector is too low 

Solution:

 Ensure that the pipe and detector flow rates are within the required 

minimum (25+ ltr/min per pipe or 50+ ltr/min for whole detector) using the “Detailed Status” view in VSC and make appropriate 
adjustments to the pipe network and/or VLI detector. 

Fault 321

 – Flow detected in pipe configured as unused 

Solution:

 In VSC, ensure you have enabled/selected the correct pipes in 

use. Also ensure that the unused inlet ports on the VLI are plugged/capped. 

Fault 322

 – A/C Mains GPI Input failure 

Solution:

  There are two solutions available to solve fault 322, they are detailed below. 

Fault 329

 – Intelligent Filter Fast Dilution Failure 

Solution:

 Let the detector run for around 15 minutes ensuring that the pipe flow 

rates are within the required minimum (25+ ltr/min per pipe or 50+ ltr/min for whole detector) , ignore the faults but reset the detector 
at 15 minutes after the power-up. Then normalize the detector flow and ensure the detector is returning a flow rate of 25+ ltr/min per 
pipe or 50+ ltr/min for the whole detector. 

 

AUTHORISED DISTRIBUTOR OF VESDA 

www.flamestop.com.au | [email protected]

Содержание VESDA VLI

Страница 1: ...ia a standard local Type B USB port This type of USB cable is most commonly used with USB printers The connector that plugs into the computer is known as Type A The USB cable is NOT included with the...

Страница 2: ...ferential where the exhaust pipe needs to go back to the sampling area keep the exhaust pipe length at a minimum Connect the VLI to the installed pipe network select relevant pipes in use through VSC...

Страница 3: ...he list of available detectors then select Next 9 Enter a unique name for the device then select Finish 10 Go to the Connection menu and select Open Connection and view next the Bacnet USB connection...

Страница 4: ...monitoring is required use the Detector GPI Ensure that Detector GPI is connected in such a way that voltage 5V appears on its terminals for GPI activation How to clear fault 322 on VLI 880 If fault...

Страница 5: ...UIDE For internal use only Authored by Manuel Espaillat 5 Double click again on VESDA VLI on left and select Input outputs you will get following warning Press OK you will get the following screen AUT...

Страница 6: ...nternal use only Authored by Manuel Espaillat 6 Change VESDAnet Card GPI to Reset as shown below Press OK double click VEASDA VLI on left again will get following screen and then select Empty under IF...

Страница 7: ...SER INDUSTRIAL VLI QUICK SETUP TECHNICAL GUIDE For internal use only Authored by Manuel Espaillat 7 Then press OK then reset detector fault 322 will clear AUTHORISED DISTRIBUTOR OF VESDA www flamestop...

Отзывы: