VESDA VLC-EX Product Guide
VESDA by Xtralis
12
www.xtralis.com
3.5
Relay settings and conditions to change states
Table 3-4: Default relay settings and conditions to change state
Relay #
Relay
Condition for relay to change state
1
Fault
This relay is de-energized when one of the following
conditions occur:
l
Fault found on detector or on VESDAnet loop
l
Air flow normalization is initiated
l
System isolation is initiated
When the Overlay Alert function has been selected,
this relay is de-energized once the Alert threshold is
initiated
2
Pre-Alarm
This relay is energized once the Pre-Alarm
threshold is initiated
3
Fire
This relay is energized once the Fire alarm
threshold is initiated
3.6
Auxiliary / GPI Terminals
The Bias, Reset (GPI) and LED terminals are located on the termination card (refer to Figure 6-1 on page 19
and Figure 6-2 on page 20). These terminals have the following functions:
l
Bias Terminals:
These output terminals provide a 10 VDC supply to initiate the reset input terminals via
a remote reset/isolate switch.
l
LED Terminals:
These output terminals provide a 5 V, 15 mA DC supply via a 220 ohm resistor to power
a remote LED.
l
Reset (GPI) Terminals:
These terminals are also known as the General Purpose Input (GPI) and are
used for Reset, Mains OK or Standby functions. The input terminals require a voltage supply between 5
V and 24 VDC to operate. The voltage input to these terminals is isolated from the system by an opto-
coupler device. Connect the Reset (+) terminal to the positive output and the Reset (-) terminal to the
ground output of the external device.
Table 3-5: GPI functions
Function
State Change
Mains OK
The detector monitors the state of the
external power supply and responds to the
following conditions.
Mains OK ≥ 5 VDC is at this terminal
Mains Fail ≤ 2 VDC is at this terminal
Standby Mode
The detector Isolates and the aspirator
turns OFF when ≥ 5 VDC is at this
terminal.
No Alarms can be generated in this state
Reset Isolate
While power is applied to the GPI the
detector is isolated. In addition, the
connection of power to the GPI resets the
unit.
≥ 5 VDC Detector Isolates
≤ 2 VDC Detector Reset
Содержание VESDA VLC-500-EX
Страница 1: ...VESDA VLC EX Product Guide VLC 500 EX VLC 505 EX September 2014 Document 20755_01 Part Number 29881...
Страница 2: ......
Страница 8: ...VESDA VLC EX Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank...
Страница 24: ...VESDA VLC EX Product Guide VESDA by Xtralis 16 www xtralis com This page is intentionally left blank...
Страница 26: ...VESDA VLC EX Product Guide VESDA by Xtralis 18 www xtralis com This page is intentionally left blank...
Страница 32: ...VESDA VLC EX Product Guide VESDA by Xtralis 24 www xtralis com This page is intentionally left blank...
Страница 34: ...VESDA VLC EX Product Guide VESDA by Xtralis 26 www xtralis com This page is intentionally left blank...
Страница 36: ...VESDA VLC EX Product Guide VESDA by Xtralis 28 www xtralis com This page is intentionally left blank...
Страница 40: ...VESDA VLC EX Product Guide VESDA by Xtralis 32 www xtralis com This page is intentionally left blank...
Страница 44: ...VESDA VLC EX Product Guide VESDA by Xtralis 36 www xtralis com This page is intentionally left blank...
Страница 46: ...VESDA VLC EX Product Guide VESDA by Xtralis 38 www xtralis com This page is intentionally left blank...