VESDA-E VEU-A00 Product Guide
40
www.xtralis.com
4.3.9
Typical Wiring to Fire Alarm Control Panel (FACP)
The diagram below shows the correct way to wire VESDA-E detectors to a conventional fire alarm control
panel (FACP).
Normally Closed (NC)
Common
FIRE 1
(C)
(NO)
Normally Open
Normally Closed (NC)
Common (C)
URGENT FAULT
(NO)
Normally Open
Unmonitored GPI
(
“R
”)
Set to
eset
Dete tor
c
(NC)
(C)
(NO)
Input
EOL = Normal
Short = Fire
Open = Fault
To next detector
or End of Line resistor (EOL)
Fire Panel (FACP)
+
-
+
-
5-30VDC
The relay is
energised on reset.
Relay shown energized which
is the no-fault condition
Figure 4-37: Typical wiring to a fire panel with EOL
4.3.10 Typical Wiring to Addressable Loop Module
This wiring example is for wiring VESDA-E detectors to a typical third party Input/Output Loop module 3
inputs 1 output.
Note:
These are example drawings. Refer to the appropriate product manual for the exact wiring details of
the third party equipment.
Normally Closed (NC)
Normally Open (NO)
Normally Open (NO)
Normally Closed (NC)
Normally Open (NO)
Fire Input
EOL* = Normal
Short = Fire
Open = Wiring Fault
EOL* = Normal
Short = Fire
Fault Input
EOL* = Normal
EOL*
EOL*
EOL*
(NC)
(NO)
Monitored GPI
(Set to ”
Mains OK”)
PSU
+
-
+
-
5-30VDC
(NC)
(NO)
This shows normal operation (no fault).
EOL*
Relay shown energized which
is the no-fault condition
EOL* = Normal
Open = Wiring Fault
3 Inputs 1 Output Loop Module
*EOL: End of Line Resistor
To next detector
Unmonitored GPI
(Set to “Reset”)
Detector
Fire 1
Common (C)
Normally Closed (NC)
Action
Common (C)
Fault
Common (C)
Short = PSU Fault
Pre Alarm
Open = Wiring Fault
Short = Detector Fault
Open = Wiring Fault
(C)
The relay is
energised
on reset
To FACP
(C)
The power supply’s fault reporting
relay is energized.
Figure 4-38: Input/Output Loop Module with EOL
4.3.11 Typical Wiring for Monitored GPI for PSU Monitoring
The diagram below shows the correct way to configure power supply monitoring. It also shows where an End
Of Line (EOL) resistor is correctly installed. Refer to Section 4.3.8 on page 39 for further information.
Содержание VESDA-E VEU-A00
Страница 1: ...VESDA E VEU A00 Product Guide November 2018 Document 22061_12 Part Number 30275 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A00 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 20: ...VESDA E VEU A00 Product Guide 14 www xtralis com This page is intentionally left blank ...
Страница 52: ...VESDA E VEU A00 Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 80: ...VESDA E VEU A00 Product Guide 74 www xtralis com This page is intentionally left blank ...
Страница 98: ...VESDA E VEU A00 Product Guide 92 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A00 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 112: ...VESDA E VEU A00 Product Guide 106 www xtralis com Z zone 57 59 77 101 ...