![Xtralis VESDA-E VEU-A00 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/xtralis/vesda-e-veu-a00/vesda-e-veu-a00_product-manual_890683015.webp)
VESDA-E VEU-A00 Product Guide
www.xtralis.com
9
2.7
Specifications
Specification
Value
Supply Voltage
18 to 30 VDC (24 VDC Nominal)
Power Consumption @24 VDC
Aspirator
Setting 1
Setting 5
Setting 10
Power (Quescent)
7.0 W
8.8 W
14.7 W
Power (in Alarm)
7.8 W
9.6 W
15.5 W
Dimensions (WHD)
350 mm x 225 mm x 135 mm
(13.8 in x 8.9 in x 5.3 in)
Weight
4.83 kg (10 lbs 6 oz)
Operating Conditions
Please consult your Xtralis representative for
information on operation outside these parameters
or where sampled air is continually above 0.05%
obs/m (0.015% obs/ft) under normal operating
conditions.
Temperature:
l
Ambient:
0°C to 39°C (32°F to 102°F)
l
Sampled Air:
-20°C to 60°C (-4°F to 140°F)
l
Tested to:
-20°C to 55°C (-4°F to 131°F)*
* UL:-20°C to 50°C (-4°F to 122°F)
Humidity:
l
10-95% RH, non-condensing
Storage Conditions
(Non-operational)
l
Humidity:
Dry (<95%)
l
Temperature:
0° to 85°C
l
Must not be exposed to sunlight or other radiation sources
Sampling Pipe Network
l
Maximum length per pipe when using four straight
pipes:
100 m (328 ft)
l
Maximum total pipe length (with branches):
800 m
(2,625 ft)
l
Pipe Modeling Design Tool:
ASPIRE
l
Minimum airflow per pipe:
15 l/m
Note:
Standards compliance of a particular pipe network
must be determined using ASPIRE.
Inlet Pipe Size
l
External Diameter:
25 mm or 1.05 in (3/4" IPS)
Exhaust Pipe Size
l
External Diameter:
25 mm or 1.05 in (3/4" IPS) via
adaptor
Relays
l
7 programmable relays
l
Contacts rated 2A @ 30 VDC (Resistive)
l
Programmable to latch or not latch alarm or fault states
IP Rating
IP 40
(not UL tested)
Mounting
Upright or inverted
Cable Access
4 x 26 mm (1 in) ports
Cable Termination
Screw terminal blocks (0.2-2.5 sq mm, 24-14 AWG)
Interfaces
l
USB (Type 2)
l
Ethernet (RJ45)
l
WiFi, 802.11 b/g/n
Dynamic Range
0.0002%/m to 20% obs/m (6.25% obs/ft to (0.00006% obs/ft)
Sensitivity Range
0.001 to 20% obs/m (0.0003 to 6.25% obs/ft.)
Table 2-2: VEU-A00 Detector Specifications
Содержание VESDA-E VEU-A00
Страница 1: ...VESDA E VEU A00 Product Guide November 2018 Document 22061_12 Part Number 30275 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A00 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 20: ...VESDA E VEU A00 Product Guide 14 www xtralis com This page is intentionally left blank ...
Страница 52: ...VESDA E VEU A00 Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 80: ...VESDA E VEU A00 Product Guide 74 www xtralis com This page is intentionally left blank ...
Страница 98: ...VESDA E VEU A00 Product Guide 92 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A00 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 112: ...VESDA E VEU A00 Product Guide 106 www xtralis com Z zone 57 59 77 101 ...