VESDA-E VES-A10-P Product Guide
78
www.xtralis.com
0.08
2
%/ft = 0.04 %/ft
Example 2:
Fire 1
Pipe 1
0.3 %/m (0.1%/ft)
Pipe 2
0.25%/m (0.08%/ft)
Pipe 3
0.4%/m (0.12%/ft)
Pipe 4
0.2%/m (0.06%/ft)
Set the lowest alert threshold to no higher than lowest Fire 1/ #pipes in use.
E.g.:
0.2
4
%/m = 0.05 %/m
Or
0.06
4
%/ft = 0.015 %/ft
Check the lowest alert threshold is as recommended after executing AutoLearn or changing the
number of pipes in use or returning the detector to factory default configuration.
6.1
AutoLearn Smoke
AutoLearn Smoke is initiated by using Xtralis VSC or the AutoConfig button located on the main board of the
detector.
During the AutoLearn Smoke process, the detector determines the average smoke and peak smoke
obscuration levels and sets suitable alarm thresholds for the operating environment. This process will
minimize nuisance alarms due to normal environmental background variations.
During the learning cycle, if an alarm condition occurs, AutoLearn will not complete its cycle. In this situation
the user must restart the AutoLearn process. If AutoLearn is halted, the alarm thresholds will be left at the
previous settings.
Conditions experienced during learning are assumed to be representative of normal operating conditions.
The AutoLearn Smoke learning times can be set between 15 minutes and 16 days, with the default being set
to 14 days.
If AutoLearn is running during the changeover period from Day to Night Thresholds, make sure that AutoLearn
runs for at least an hour in both the Day and Night periods.
Alarm Level
AutoLearn Smoke Range
Alert
0.005% – 2.0% obs/m (0.0016% - 0.625% obs/ft)
Action (Pre-Alarm) 0.005% – 2.0% obs/m (0.0016% - 0.625% obs/ft)
Fire1 (Alarm)
0.010 % – 2.0% obs/m (0.0031% - 0.625% obs/ft)
Fire2
0.020 % – 20.0% obs/m (0.0063% - 6.25% obs/ft)
Table 6-1: AutoLearn Smoke range
For code-specific information, see Codes and Standards Information for Air Sampling Smoke Detection on
page iii.
Содержание VESDA-E VES-A10-P
Страница 1: ...VESDA E VES A10 P Product Guide VES A10 P 4 Pipes August 2019 Document 33794_02 Part Number 30915 ...
Страница 2: ......
Страница 10: ...VESDA E VES A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VES A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 52: ...VESDA E VES A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VES A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 86: ...VESDA E VES A10 P Product Guide 80 www xtralis com This page is intentionally left blank ...
Страница 103: ...VESDA E VES A10 P Product Guide www xtralis com 97 Figure 7 21 Undo Sampling Module screws ...
Страница 108: ...VESDA E VES A10 P Product Guide 102 www xtralis com ...
Страница 110: ...VESDA E VES A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 114: ...VESDA E VES A10 P Product Guide 108 www xtralis com This page is intentionally left blank ...
Страница 120: ...VESDA E VES A10 P Product Guide 114 www xtralis com This page is intentionally left blank ...
Страница 126: ...VESDA E VES A10 P Product Guide 120 www xtralis com Z zone 57 58 81 115 ...