VESDA-E VEP-A10-P Product Guide
www.xtralis.com
59
Command
Description
Execute From
A button
on the
Detector
Xtralis VSC
Software
Start Minor Fault Test
Generates a minor fault on the detector and de-
energizes the fault relay for 2 minutes.
Start Alarm Test
Simulates full scale smoke level which causes the
Alert, Action , Fire 1 and Fire 2 alarm conditions to
occur.
Alarm relays will energize unless the detector is
disabled.
Start Air Flow Fault Test Tests the air flow sensing system by shutting down
the aspirator.
Start Relay Test
Tests the available relays by activating and
deactivating as required.
Start LED Test
Tests each LED by cycling through all LEDs on the
detector display panel.
Return to Factory
Defaults
Restores the configuration of the detector to the
initial factory default values.
Set System Date and
Time
Sets the detector date and time.
Table 5-2: Detector Commands (continued...)
Содержание VESDA-E VEP-A10-P
Страница 1: ...VESDA E VEP A10 P Product Guide VEP A10 P 4 Pipes April 2016 Document 22071_11 Part Number 30311 ...
Страница 2: ......
Страница 10: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEP A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEP A10 P Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEP A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEP A10 P Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 108: ...VESDA E VEP A10 P Product Guide 102 www xtralis com This page is intentionally left blank ...
Страница 114: ...VESDA E VEP A10 P Product Guide 108 www xtralis com Z zone 58 60 79 103 ...