![Xtralis VESDA-E VEP-A10-P Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/xtralis/vesda-e-vep-a10-p/vesda-e-vep-a10-p_product-manual_890679006.webp)
VESDA-E VEP-A10-P Product Guide
iv
www.xtralis.com
Regional Regulatory Requirements and Notices
UL and ULC
For open area, open area high velocity and duct protection the fire alarm threshold (setting) that initiates an
evacuation signal must be set such that the sensitivity of each sampling hole is more sensitive than 10%/m
(3.2 %/ft) as determined by the ASPIRE software.
European Installations
The product must use a power supply conforming to EN54: Part 4.
EN 54-20
The product must use a power supply conforming to EN 54-4.
The product is compliant with EN 54-20 sensitivity requirements provided the following conditions are met:
l
For a Class A detector, hole sensitivity must be better than 1.5% obscuration/m and transport time less
than 60 seconds
l
For a Class B detector, hole sensitivity must be better than 3% obscuration/m and transport time less
than 90 seconds
l
For a Class C detector, hole sensitivity must be better than 8% obscuration/m and transport time less
than 110 seconds
These limits should be verified using ASPIRE during the design of the sampling pipe network.
The product is compliant with EN 54-20 flow monitoring requirements provided the following conditions are
met:
l
The minor low and minor high flow thresholds should be set at 85% and 115% respectively
l
The flow through the detector predicted by ASPIRE must be greater than 20 L/m.
Product Listings
Regional approvals listings and regulatory compliance vary between product models. Refer to www.xtralis.com for
the latest product approvals matrix.
Document: 22071_11
Part Number: 30311
Содержание VESDA-E VEP-A10-P
Страница 1: ...VESDA E VEP A10 P Product Guide VEP A10 P 4 Pipes April 2016 Document 22071_11 Part Number 30311 ...
Страница 2: ......
Страница 10: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEP A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEP A10 P Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEP A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEP A10 P Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 108: ...VESDA E VEP A10 P Product Guide 102 www xtralis com This page is intentionally left blank ...
Страница 114: ...VESDA E VEP A10 P Product Guide 108 www xtralis com Z zone 58 60 79 103 ...