Ducts Application Note 

 

VESDA-E 

35424_02 

 

 

Key Design Considerations 

1.3.1  VESDA-E VEP-1P 

The following should be considered when designing a VESDA-E VEP-1P for duct protection: 

 

All inlet and exhaust pipes must be sealed at their far end with an end-cap. 

 

The holes on the inlet and exhaust pipes should be facing the airflow as shown in the above figures. 
Holes with the same orientation eliminate unwanted flow faults associated with cyclical operation, 
maintenance or power failure of the duct system. However, in some industrial applications, where the 
quality of air inside the duct is poor, it is recommended that all holes on the inlet and exhaust pipes face 
downstream, that is, 180° to the incoming airflow). 

 

The pipes should always be held in position at the duct walls with fittings such as rubber grommets. 
Silicon is recommended, to ensure an airtight seal. 

 

Regardless of duct width, the exhaust pipe must have 4 × Ø10 mm (13/32 inches) holes. 

 

Never simultaneously sample from multiple ducts or ambient environments with the same the detector. 

1.3.2  VESDA-E VEA 

The following should be considered when designing a VESDA-E VEA for duct protection: 

 

Sampling points install in duct pressures within -30Pa to +30Pa. 

 

Maximum differential pressure (DP) of 30Pa between sampling points on same VEA unit. 

 

The exhaust of the VEA unit must be within a pressure range -30Pa to +30Pa. 

 

 

Содержание VESDA-E VEP-1P

Страница 1: ...DUCTS APPLICATION NOTE February 2021 Doc No 35424_02...

Страница 2: ...mation contained in this document will assist you when designing VESDA E systems for this type of application Note This system is not suitable for use in flexible ducts Related Products VESDA E VEP 1P...

Страница 3: ...1 3 2 VESDA E VEA 5 2 VESDA E System Installation 6 Environmental Conditions 6 2 1 1 VESDA E VEP 1P 6 2 1 2 VESDA E VEA 7 Key Installation Considerations 7 3 VESDA E System Commissioning 8 Hole Orien...

Страница 4: ...a quarter of the height of the duct Figure 1 Side view of the inlet and exhaust pipe positions for a small ventilation duct A top view of the above installation is shown below Figure 2 The number of...

Страница 5: ...m 0 66 ft 1 1 2 VESDA E VEA Return air sampling is achieved with microbore tubes for VEA system inserted in the return air duct behind the exhaust grill it is recommended the tubes are installed facin...

Страница 6: ...commended that the inlet pipe of the smoke detector be in two branches The figure below Figure 5 shows a side view of a duct section with the relative insertion points for the inlet and exhaust pipes...

Страница 7: ...le spacing is 0 4 m 1 3 ft The exhaust pipe must have 4 10 mm 13 32 inch sampling holes regardless of the width of the duct These holes should be located in the middle of the duct width at least 50 mm...

Страница 8: ...uct is poor it is recommended that all holes on the inlet and exhaust pipes face downstream that is 180 to the incoming airflow The pipes should always be held in position at the duct walls with fitti...

Страница 9: ...tside the duct where the detector is to be installed and the temperature of the air inside the sampling pipes of the detector You should measure the temperature and humidity both inside the duct and i...

Страница 10: ...ream of humidifiers heating coils and filters Upstream of fresh air intakes For a smoke detector mounted on the duct ensure there are no tangible vibrations when the duct system is in full operation I...

Страница 11: ...nd then record the Flow 5 Insert the inlet and exhaust smoke detector pipes in the duct with the holes facing the airflow and record Flow at the smoke detector 6 Slightly rotate the pipes so that the...

Страница 12: ...xible tube containing water as shown Figure 9 ensuring all connections are airtight 2 Face the holes on both the inlet and exhaust pipes to the airflow Slightly rotate the pipes so that the water leve...

Страница 13: ...tector Cover the electronics during this test with a sheet of paper 5 Introduce smoke inside the detector s interior housing using a smoke can 6 Place the smoke can s nozzle 0 5 m 1 5 ft away from the...

Страница 14: ...1 Check flow readings at the smoke detector s Differences in flow readings from those of previous site visits require further investigation such as inspection of the pipes sampling tubes integrity for...

Страница 15: ...mendation on system design Xtralis has not assessed the recommendation on system design for compliance with any codes or standards that may apply nor have any tests been conducted to assess the approp...

Отзывы: