ICAM Commissioning Guide

ICAM by Xtralis

16

www.xtralis.com

5.1.2

Pipe Integrity Smoke Testing

This test should be used to test pipe integrity in any typical customer site. This method is suitable for the
testing of standard sensitivity fire detection systems. You will need a smoke source, a stopwatch, and a fire
extinguisher.

It is easy to see an increase of smoke on detectors that have a display module fitted.

1. Ensure that the local fire panel is isolated from the external fire reporting equipment and that any

automatic extinguishing or suppressant systems are also isolated.

2. Introduce smoke directly into the furthest sample hole in the pipe run, and start the timer.
3. Stop the timer when the detector registers the smoke and record the results.
4. Compare the time expected by ASPIRE with the actual recorded time. If the actual recorded time is 20%

or greater than the expected time, check the pipe for breaks.

5.1.3

Smoke Pellet Testing

This method is suitable for the testing of high and enhanced sensitivity environments. Smoke is produced by
lighting a number of small smoke pellets. You will need smoke pellets, a tray, and a method to time the test. If
you are testing in an area with a high roof you may also require a radiated heater to fix stratification problems.
Refer to Section 5.1.1 for further information.

1. Ensure that the local fire panel is isolated from the external fire reporting equipment and that any

automatic extinguishing or suppressant systems are similarly isolated.

2. Cover a metal tray with kitchen foil.
3. Set the heater close to the tray. This is required to make the smoke rise.
4. Put the smoke pellets on a metal tray. The number of pellets to use is determined by the system designer.
5. Put something under the tray to protect the floor from damage.
6. If you are testing a high roof area turn the heater on.
7. Light the pellets with a match, and start the timer.
8. Acceptable detector response time is specified in local codes and standards or as per the system design.

Figure 5-1: Smoke Pellet Testing

For further information on Smoke Pellet Testing, refer to BFPSA or FIA CoP standards.

Содержание ICAM IFT

Страница 1: ...ICAM Commissioning Guide May 2018 Document 14972_02 Part Number 29303...

Страница 2: ......

Страница 3: ...uipment damage Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only persons tr...

Страница 4: ...before you receive the appropriate training may void the warranty Document Conventions The following typographic conventions are used in this document Convention Description Bold Used to denote emphas...

Страница 5: ...fore going to the Site 7 3 2 ICAM Commissioning Form Prerequisites 7 3 3 Once on Site 7 4 System Configuration and Setting Thresholds 9 4 1 IFT Detector Configuration 10 4 2 ILS Detector Configuration...

Страница 6: ...ICAM Commissioning Guide ICAM by Xtralis 2 www xtralis com This page is intentionally left blank...

Страница 7: ...CAM system installation It forges together the elements of designing and installing a pipe network installing the detectors cabling for power and communications and the powering up of the system Your...

Страница 8: ...ICAM Commissioning Guide ICAM by Xtralis 4 www xtralis com This page is intentionally left blank...

Страница 9: ...r site Gather site information Obtain a copy of l Pipe network design records l Pipe network installation form l Site plans and pipe layout plans Start to fill in l Commissioning forms l Any regulator...

Страница 10: ...ICAM Commissioning Guide ICAM by Xtralis 6 www xtralis com This page is intentionally left blank...

Страница 11: ...Section 5 1 10 Optional Digital manometer if sample hole pressure is required to be measured l Wide Bore networks Max range 3kpa l Narrow Bore networks 0 20kpa at the end of the recommended length of...

Страница 12: ...ors l All LEDs turn on then off about five times and the sounder beeps about five times l Aspirator starts l Fault indicators are activated for current faults l Smoke levels are indicated on the bargr...

Страница 13: ...y be configured via the detector s user interface Where possible air flow thresholds and smoke alarm thresholds should be determined using ASPIRE pipe network configuration software When an ICAM detec...

Страница 14: ...ntrol functions require the user to enter an Access Code There are several levels of access 1 Operator 2 Level 1 3 Level 2 4 Level 3 Access Code Levels are downwards applicable for example if a User e...

Страница 15: ...relating to air flow is set through the CONFIGURE menu option Some of the key parameters are l FLOWDEL Flow Fault Delay 1 to 60 s l FLOWHI FLOWLO High and low air flow limits for declaring a Flow Faul...

Страница 16: ...ED flashes continuously to indicate the function selected To enable updates to the system enter the three digit access code 510 To enter numbers into the system each number must be sequentially select...

Страница 17: ...y for 1 sec to initialize function selection Press and release SELECT key to sequentially step through functions Press and release CHANGE key to modify setting The relevant LED flashes continuously to...

Страница 18: ...ICAM Commissioning Guide ICAM by Xtralis 14 www xtralis com This page is intentionally left blank...

Страница 19: ...Very sensitive sites can use the electrical overload PVC coated wire burn test or the smouldering test coil test UK customers can refer to BS 6266 BFPSA Code of Practice Appendix A for system perform...

Страница 20: ...suitable for the testing of high and enhanced sensitivity environments Smoke is produced by lighting a number of small smoke pellets You will need smoke pellets a tray and a method to time the test I...

Страница 21: ...esign Legend A 500mm 20 in B Kitchen foil in tray C 20mm 0 874 in Figure 5 2 Polyurethane Mat Smoke Test 5 1 5 Wire Burn Smoke Testing This test is performed by using a transformer to overload the pow...

Страница 22: ...g the above test procedure Enter the following results on the commissioning form l Transport Time Introduce smoke at the furthest sampling hole from the detector The time taken in seconds for the smok...

Страница 23: ...5 2 Testing Devices The outputs for the IFT detectors can be tested using a diagnostic test that is accessed through the TEST OUTPUTS menu function For more information please see the IFT Product Gui...

Страница 24: ...ICAM Commissioning Guide ICAM by Xtralis 20 www xtralis com This page is intentionally left blank...

Страница 25: ...ssioning forms are complete and all relevant sections have been filled in l If you have used Xtralis VSC select the Device or Address then select File Print to print out a copy of configuration detail...

Страница 26: ...ICAM Commissioning Guide ICAM by Xtralis 22 www xtralis com This page is intentionally left blank...

Отзывы: