Xtralis VESDA LCD Programmer Product Guide
Xtralis
VESDA
®
34
www.xtralis.com
103.
Factory Defaults
-
•
Factory Defaults - To restore factory defaults, highlight Restore and press
.
•
Defaults OK - Highlighting Start and pressing
will acknowledge Factory
Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
DST
ADM
104.
Communications
- The Communications screen allows settings for:
•
Net Delay - This function sets the maximum time for a message to travel around
the network and return to the originating device. If the message does not return
within the prescribed time, it is presumed lost and will be resent
•
Prof. Port - This allows you to assign a preferred port for communication
•
Health Check - This function sets the frequency of health-check messages sent
around the system
•
Open-ended - In an open-ended VESDAnet loop select the port that is not
connected to the VESDAnet loop.
DST
105.
Miscellaneous
-
•
UL Version - A
against this indicates that the device is set to meet UL
specifications.
•
Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms
•
Latch Faults - This provides a YES/NO option to latch/unlatch all Faults
•
GP Input - The GP Input permits setting the general purpose input functions.
For details on GPI functions please refer to the VLP
Detector Guide
.
ADM
DST
106.
Ancillary Devices
- Should be put under the same flow line as detectors. Select
the device by highlighting it and press
.
USR
107.
Display/Relays
- Should be put under the same flow line as detectors. Select the
Display/Relay and press
.
USR
108.
Status
- Displays the current status of the Display/Relay
•
Faults - List of faults generated for Display/Relay connected to VESDAnet
•
SW Version - Displays the software version of the Display/Relay
•
Cfg Code - This is a configuration code set during production
USR
Scrn
No.
Description
Min.
Access
Level
↵
↵
Parameter
Default
Minimum
Maximum
Network delay
15 seconds
10 seconds
45 seconds
Preferred port
A
N/A
N/A
Health check
45 seconds
40 seconds
60 seconds
Open - ended
none
N/A
N/A
Parameter
Default
UL Version
Enabled
Latch Alarm
Enabled
Latch Fault
Enabled
↵
↵