Relay Assignments
- Each relay is allocated a screen. In their respective screens
assign the relevant alarm, fault or isolate function. Multiple functions can be
assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent
Fault and Fire 1 functions respectively. Additional functions may be assigned to
Relays 3 and 6. Use the
key to assign or de-assign functions.
ADM
36.
Diagnostics
- It is possible to conduct alarm and fault tests through sub-menus of
this screen.
•
Alarm Test - This causes the detector to generate a Fire 2 condition
•
Fault Test - This causes a system fault for 30 seconds
•
Flow Fault - This turns the aspirator off for 30 seconds causing an air flow fault
•
Relay Test - (Refer to Screen 37).
ADM
37.
Relay Test
- This allows testing each relay by turning it ON and OFF.
ADM
38.
Factory Defaults -
•
Factory Defaults - To restore factory defaults, highlight Restore and press
.
•
Defaults OK - Highlighting Start and pressing
will acknowledge Factory
Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
DST
ADM
39.
Communications
- The Communications screen allows settings for:
•
Net Delay - This function sets the maximum time for a message to travel around
the network and return to the originating device. If the message does not return
within the prescribed time, it is presumed lost and will be resent
•
Pref. Port - This allows you to assign a preferred port for communication
•
Health Check - This function sets the frequency of health-check messages sent
around the system
•
Open-ended - In an open-ended VESDAnet loop select the port that is not
connected to the VESDAnet loop.
DST
Scrn
No.
Description
Min.
Access
Level
↵
Parameter
Default
Fire 2
Relay 7
Fire 1
Relay 6
Action
Relay 5
Alert
Relay 4
Urgent Fault
Relay 3
Minor Fault
Relay 2
Isolate
Relay 1
↵
↵
Parameter
Default
Minimum
Maximum
Network delay
15 seconds
10 seconds
45 seconds
Preferred port
A
N/A
N/A
Health check
45 seconds
40 seconds
60 seconds
Open - ended
none
N/A
N/A