In a system comprising a single Xtender, the connection of the RCC-02 or RCC-03 units may be
conducted without stopping the Xtender (hot plug).
The communication bus will be used to interconnect other Xtender inverters in the case of a multi-
unit application or to connect other types of users who have the proprietary protocol of Studer
Innotec. In these cases, the plug-in of interconnected units is done only after the switch-off of the
installation, by disconnecting the battery or by using the main "ON/OFF" button (1) if present.
The 2 switches for the communication bus termination, "Com. Bus" (4) both remain in position
T (terminated) except when both connectors are in use. In this case, and only in this case,
both must be placed in the O open position. If one of the two connectors is not in use, the
two termination switches (14) will be in position T.
5
XTENDER PARAMETER SETTINGS
Xtender inverters have by default a number of factory settings and most of them can be modified
by the user or installer. Some basic parameters mentioned in Chapter 7 must be set at the
commissioning. For XTM and XTH models, this setting must be done by connecting the remote control
described in RCC-02/03 chap. 7.3.1 - p. 36. For the XTS model, four of them can be done directly in
the unit before powering up.
The remote control "RCC-02/-03" manual contains a complete description of available features and
associated parameters. The manual is available to download from the website www.studer-
innotec.com.
When the Xtender is connected to the remote control RCC-02/-03 or another Xtender compatible
device (VarioTrack, BSP etc.) it is possible that their software versions differ. It is important to harmonize
the software versions of all Xtender compatible products in a system. The update is made by the
remote control RCC-02/-03 from an SD card with a firmware version at least corresponding to the
most recent device.
5.1
B
ASIC PARAMETER SETTINGS IN THE
XTS
For XTS models, 4 parameters / basic functions can be modified
directly on the compartment inside the door. All other
parameters can be adjusted, if necessary, via the remote
control RCC-02/03.
•
The battery current charge {1138} as described in chap.
7.3.2 - p. 30 by using the potentiometer (16)
•
The max. AC source (input limit) {1107} as described in chap. 7.2.2 - p. 27 by using the
potentiometer (18). The potentiometer can be adjusted between 0 – 16 Aac.
•
The source current assistance (Smart boost) function {1126} as described in chap. 7.2.2.1 - p. 27 by
using the slide button (19)
•
The type of detection of AC-input loss (UPS) Fast/Tolerant/slow {1552} as described in chap. 7.2.1-
p. 27 by using the slide button (20)
These manual adjustments can be prevented using parameter {1551} on the remote control RCC-
02/-03. These values will then be defined by parameters from the remote control. If the parameter
{1551} is set to "yes" the buttons 16, 18, 19 and 20 remain inactive even if the remote control RCC-02/-
03 and/or the communication module Xcom-232i are removed after the initial setting.
Before opening the enclosure, it is mandatory to
disconnect all AC and DC sources (battery) of the
product to avoid any risk of electrical shock.
Model Potentiometer grading, min - max
XTS12V 0 – 35 Adc
XTS24V 0 – 25 Adc
XTS48V 0 – 12 Adc