Connection example of 3 doors
Door contact
OUT
IN
electric strike (fail close)
Emergency
button
Box Tamper
Push button
Push button
Electromagnetic Lock 12V/600mA max
Address 0
12V/600mA max
Reader
Reader
Door contact
Address 1
electric strike (fail open)
Network
Alarm siren
or
flash siren
Power supply 14,2V
See user manual
12V battery
12V/600mA max
Address 0
Address 1
Example of a door with 2 r electric strike fail close
1. The readers for Doors 1.0 and 2.0 must be at address 0 and
those for Doors 1.1 and 2.1 at address 1.
2. For doors equipped with 2 readers, one must be at address
0 and the other at address 1.
3. The function of OUT1 and OUT2 can be configured in the
software
4. In1 & In2: Connect to GND by a volt-free contact to activate
the input
5. LIYCY cable, twisted pair, up to 80m.
If more than 80 m. are needed, then termination resistors(120
ohm) may be required at both ends of the RS485 line, while
taking into consideration the lengths proposed on our web
site.
6. Alarm cable 2x0,22
7. The cross section of the cable depends on the current
needed by the lock
Note
: The elevators relay boards (WS4-RB-12) are connected
on the same Rs485 lines as the readers.
This product herewith complies with requirements of EMC directive 2014/30/EU.
In addition it complies with RoHS2 directive EN50581:2012 and RoHS3 Directive 2015/863/EU.
Example of a door with 1 electric strike fail open
Example of a door with 1 electromagnetic lock