In order to prevent the Heat Exchanger from freezing when the outside temperature is low, a frost protection monitor has been integrated  

 

Factory setting (No user adjustment): 

 

If the temperature in the outgoing air duct falls below 4°C the supply air Fan will stop (the exhaust air Fan will   remain on). When the outgoing air temperature reaches 7°C 
again the supply air Fan comes back on automatically. 

 

Fan fault safety shut down

 

Should the supply air Fan fail the exhaust air Fan will switch off automatically. 
 
 
 
 
 
 
 
 
 
 

 

9. Pre Heater Accessory

  

 
When the incoming air temperature drops below the set temperature  
(0°C to 3°C), the Defrost Pre-Heater Unit will switch on and warm                                                                               the incoming air prior to it arriving at the MVHR to pre-
vent ice forming  
within Exchanger.  
  
When the incoming air temperature rises above the set temp.                                                                                 (0°C to 3°C), the defrost heater unit will switch off. 
 
 
 
 

10. Maintenance 

 

 

10.1 Filters 

The MVHR should never be operated without Filters. However, depending on the actual volume of contaminants  
in the environment, the MVHR Filters need to be checked and cleaned at least twice a year and replaced at least on an annual basis. The original external / exhaust F5 
quilted filters are enclosed in a frame. Contact details for purchasing new filters or servicing by Xpelair approved technicians can be found on the back of this booklet. 
 

10.1.1 Removing and re-fitting the filters 

 

Important:

  A planned filter replacement regime protects the recuperator from needing to be cleaned.  

Before removing the recuperator disconnect the MVHR from the mains supply. 

 

1.  Remove  filter access covers using finger grip 
 
2.  Remove the two Filters 

 

3.  Insert cleaned or new Filters. Filters can be cleaned by gently knocking together to remove dust/dirt 

 

4.  Replace the Access covers 

 

5.  The MVHR is ready to recommence operation. 

 
 

 

 

 
 
 
 
 

11.  Air Filter Box (Optional accessory) 

 
The MVHR is fitted with F5 Filters as standard. To protect allergy  
sufferers against environmental pollution, for example, it may be  
useful to install a filter box with finer Filters. These Filters are  
designed to offer the longest service life and lowest pressure loss 
and are installed in a box immediately after the supply air outlet. 
Class F7 Panel Filters are available as the filter elements.  

 

The Filters fitted in the Air Filter Box should be checked for cleaning/ 

 

 

Содержание Xcell Stratum S120Q

Страница 1: ...Installation and user manual Xcell Stratum S120Q Mechanical Ventilation Unit with Heat Recovery Please ensure these instructions are kept safe and accessible at all times...

Страница 2: ...7 5 6 Installation dimensions 8 6 Technical Data 8 6 1 Technical data 8 6 2 Accessories 8 6 3 Replacement filters 9 7 Electrical Wiring Diagram 9 7a Electric wiring 2 way switch 9 7b Electric wiring...

Страница 3: ...s they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Ensure that all relevant safety precautions correct eye protection and protec...

Страница 4: ...heated external air is distributed into the house and the cooled exhaust air is ducted out of the building 4 3 MVHR installation planning MVHR system designs must comply with the current standards go...

Страница 5: ...rong odours which could then permeate into the MVHR and contaminate the fresh air supplied from the MVHR unit The following must also be met Access is required for maintenance work e g changing the fi...

Страница 6: ...ters a frost protect pre heater is recommended All ducting fitted to the spigots on the MVHR should be secured via a suitable sealed duct connector to prevent air leakage e g Xpelair CPC125 91485AA Du...

Страница 7: ...d annually and cleaned if necessary A condensate drain tube 20mm and 1 0m long is supplied The water trap must be purchased separately from a local plumbing stockist 5 5 Typical installation example 1...

Страница 8: ...C 20 to 40 Dimensions without ducting W x H x D mm 550 x 240 x 510 Weight of MVHR Kg 10 Duct connections mm 125 4xDN125 Condensate drain tube connections mm 20 Filter class F5 Efficiency of Recuperat...

Страница 9: ...6 3 Replacement filters Description Part Number Replacement filters set of 2 40552AA 7 Electrical Wiring 7a Electrical Wiring to a two way switch 9...

Страница 10: ...ng a common and high or low 7 1 Set up procedure Move jumper to Test 1 position Balance system to desired normal extract rate using pot speed 1 Move jumper to Test 2 position Balance system to desired...

Страница 11: ...d and cleaned at least twice a year and replaced at least on an annual basis The original external exhaust F5 quilted filters are enclosed in a frame Contact details for purchasing new filters or serv...

Страница 12: ...MVHR is operated 7 Carefully insert the cleaned Recuperator keeping it parallel to avoid damaging the EPP housing 8 Replace the Recuperator Retaining Bracket and retaining screw 9 Switch the mains su...

Страница 13: ...13 Room air regulator valves not open wide enough Note This table may be subject to technical amendments...

Страница 14: ...four retaining screws to remove the plastic Motor Mount from the faulty fan noting the orientation of the faulty fan and it s leads in relation to the slots in the plastic motor mount f Assemble the...

Страница 15: ...ge made EXCLUSIONS This guarantee does not apply to the repair or replacement of filters accessories isolating switches electrical cable fuses and or circuit breakers or annual servicing This guarente...

Отзывы: