location of your grill (cont'd.)
CLEARANCE TO COMBUSTIBLE CONSTRUCTION (CONT’D):
• If installed under any combustible construction the area above the cooking surface of the
grill must be covered with an approved exhaust hood.
• It is highly recommended the hood be sized with a 3” overhang on all exposed sides.
• The exhaust hood shall provide no less than 1,000 CFM of proper exhaust ventilation.
• The exhaust hood must be approved for outdoor installation and used with a dedicated
GFCI branch circuit.
Page 1
5
5”
min.
30” to 36”
We recommend oversizing the hood by 3" on
each side to maximize efficiency and capture
space
For example;
A 36" Grill would require a 42" Hood
NON-COMBUSTIBLE
BACKSPLASH
REAR W
ALL
OVERHEAD CONSTRUCTION
TYPICAL EXHAUST HOOD INSTALLATION
OBSERVE ALL MINIMUM CLEARANCES
Non-Combustible Construction
Sides 12” Back 5”
Combustible Construction
Sides 14” Back 16”
Combustible Overhead Construction
Must Be Protected By An Approved Hood
Use Of An Approved Hood Is Highly
Recommended With Non-Combustible
Overhead Construction
60”
Minimum above
cooking surface to
non-combustible
overhead.
Содержание XOGRILL30L/N
Страница 1: ...GAS GRILL CARE USE INSTALLATION RESIDENTIAL USE ONLY Page 1...
Страница 8: ...Page 8 specifications xo grill 30 xo grill 36 xo grill 42...
Страница 9: ...Page 9 knob positions HIGH IGNITION POSITION HIGH IGNITION POSITION HIGH IGNITION POSITION...
Страница 44: ...parts list...
Страница 45: ...Page 45 parts diagram parts diagram...
Страница 48: ...1 800 966 8300 Visit our web site at www xoappliance com now we are cooking...