background image

INDEX

 

USER MANUAL - OPTIMA T09W 6K/10K 

 

www.xmart-ups.com 

VER.1801.25-WP+ (ENG)

 

24 

 

8.

 

START-UP 

 

 

 

INSPECTION BEFORE START UP 

 

1.

 

Make sure all wires are tightly connected to terminal block. Any loose connection will produce overheating, failures and damage to 

UPS. 

2.

 

Make sure all instructions of installation sections have been performed correctly. 

3.

 

Put the terminal block cover back in its position to avoid access to wiring 

4.

 

Check EPO port: 

 

EPO Port closed (Wired): EPO function disabled 

 

EPO  port  connected  to  an  emergency  switch:  EPO  function  available  by  activation  of  Emergency  Switch;  which  must  be 

“Normally Closed” type in order to guarantee that UPS will shut down when circuit opens.

 

5.

 

Check Maintenance Bypass Switch (MBS) located in UPS rear panel is in UPS position and its safety cover plate is duly installed. 

6.

 

Make sure all external protection devices in input and output lines are in open (OFF) position. 

 

 

SINGLE UPS - START UP PROCEDURE  

1.

 

Make sure all equipment connected to UPS are off 

2.

 

Power input lines ON at electrical board by setting Circuit Breaker to ON 

3.

 

Put Battery Bank breaker to ON (in case UPS has XBAT connected) 

4.

 

Put AC INPUT Breaker to ON in UPS rear panel. 

5.

 

LCD of UPS must turns on. UPS should adopt bypass mode.  

6.

 

Start up the UPS by pressing <ON> push button during a couple of seconds. ON button must be pressed until LCD shows the text 

“ON”. If ON 

button is released before that, UPS will not turn-on. 

7.

 

UPS will run an auto-test and few seconds later, UPS leaves By-

Pass mode to enter in Normal Online Mode, also known as “AC 

Mode”. ONLINE LED must light in green color.

 

8.

 

Switch external output breakers to ON position. 

9.

 

Power on sequentially each protected equipment. The front panel LCD should show the load increase as equipments start. 

10.

 

Once all equipment are on, the total power consumption (load) should not exceed UPS capacity. 

11.

 

At this moment UPS working under NORMAL AC-MODE and the system is supplied by UPS. 

 

NOTE 1:

 If any error or warning message is indicated in LCD, please revise Troubleshooting section of this manual.   

NOTE 2:

 UPS batteries maybe are not fully charged. UPS could require about 4 to 6 hours to recharge batteries up to 100% of their 

capacity. 

 

 

 

 

 

 

 

Содержание OPTIMA-T09W-06K-230V

Страница 1: ...ormation on this manual is property of XMART This manual Information cannot be copied or distributed totally or partially without written approval of XMART XMART can introduce modifications in their p...

Страница 2: ...PERFORMANCE STANDARDS 3 PRODUCT DESCRIPTION 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 START OPERATION INDIVIDUAL PARALLEL UPS 9 ERROR ALARMS CODES TROU...

Страница 3: ...racelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electrical...

Страница 4: ...G Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party responsible for compliance could void the user s authority to oper...

Страница 5: ...cs It is equipped with a powerful anti surge system based on MOV technology and filtering circuits to eliminate electromagnetic interferences EMI It is 100 compatible to operate connected to low quali...

Страница 6: ...ectrical shock because high DC voltage External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS DC polarity of the Battery bank must...

Страница 7: ...find voltage in input lines of the UPS so that a backfeed failure could represent an electrical shock risk for the operator An effective backfeed design must be able to open automatically all UPS AC...

Страница 8: ...in sites exposed to sun light or heat sources Temperature at operation site should never rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and an...

Страница 9: ...age is provided by battery packs by connecting 20 batteries 12VDC in series There could be some UPS models working with a different DC voltage User must check carefully XBAT voltage is compatible with...

Страница 10: ...Voltage 120Vac ISOTX Wiring min 10AWG 6mm2 AC Breaker 80A Curve D Breaker per Output 40A Curve D Max Nominal Current 60A Max Nominal Current 30A Wiring min 6AWG 16 mm2 Wiring min 10AWG 6 mm2 OPTIMA T0...

Страница 11: ...lines must be connected to electrical board using cables with required gauge INPUT OUTPUT CONNECTIONS First of all connect ground terminals to system earth Ground must always be first terminals to co...

Страница 12: ...te 120Vac outputs that can be wired in 3 different configurations 2 individual outputs120V Each output can drive 50 of total UPS power 1 output 120V By connecting 2 separate outputs in parallel This o...

Страница 13: ...lso and UPS will power off No battery mode can be adopted from bypass mode Bypass mode can be caused by any of below conditions 1 Bypass mode is adopted in case ON button has not been activated as soo...

Страница 14: ...SWITCH In case user decides to install a generic external bypass switch without a safety plate status signal the operator will be responsible of setting UPS in static bypass mode before actuating the...

Страница 15: ...ut also feeds rectifier input UPS output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output indica...

Страница 16: ...elease before required time UPS will not turn on ENTER When UPS is in configuration mode this key operates as ENTER OFF ESCAPE UPS TURN OFF Press during 2 seconds to turn UPS off SCAPE When UPS is in...

Страница 17: ...NFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also shows...

Страница 18: ...5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Power...

Страница 19: ...or changing parameters value ON ENTER Used as ENTER key to confirm modifications MUTE DOWN Used as key to navigate or changing parameters value AVAILABLE FUNCTIONS UNDER EACH OPERATION MODE FUNTION DE...

Страница 20: ...tter value of input frequency If ATO is selected output frequency will be set by input frequency read when UPS started by first time from 46 to 54 Hz will set to 50Hz from 56 to 64 Hz will set to 60Hz...

Страница 21: ...S Disable Automatic Bypass allowed but manual is prohibited Set values with keys 09 MAXIMUM RUNTIME This function sets maximum time in Battery mode 000 a 999 Max Time in minutes DIS Disable Runtime wi...

Страница 22: ...lues with keys 18 MAXIMUM CHARGER CURRENT Max current in Amps can be set by this function Available Values 1Amp 2Amp 4Amp 8Amp Factory set 2Amp NO MODIFICATIONS RECOMMENDED ONLY BY TECHNICIANS 19 BATT...

Страница 23: ...Function Disable Funci n de Convertidor de Frecuencia Desactivado ON ON Encendido OFF OFF Apagado ENA Enable Habilitado DIS Disable Des habilitado ATO Auto mode Modo Autom tico SUB Subtract Disminuir...

Страница 24: ...er input lines ON at electrical board by setting Circuit Breaker to ON 3 Put Battery Bank breaker to ON in case UPS has XBAT connected 4 Put AC INPUT Breaker to ON in UPS rear panel 5 LCD of UPS must...

Страница 25: ...eep s HIGH TEMPERATURE 1 beep s CHARGER FAILURE 1 beep s UPS BLOCKED as consequence of detecting 3 overloads in less than 30 minutes OR MBS cover REMOVED 1 beep s ALARMS ALARM CODES Battery Disconnect...

Страница 26: ...DITION ERROR CODE ERROR SYMBOL DC BUS start failure 01 DC BUS High 02 DC BUS Low 03 DC BUS unbalanced 04 INVERTER start failure 11 INVERTER High voltage 12 INVERTER Low voltage 13 SHORT CIRCUIT detect...

Страница 27: ...is not solved call technical support FAN Failure Check if fans are working properly If not call technical service EEPROM Failure Turn off and power off UPS Restart UPS If not solved call technical se...

Страница 28: ...ONTHS RECHARGE DURING 6 HOURS 12 BATTERIES CHARGER CONFIGURATION SERVICE THIS INFORMATION IS ONLY FOR QUALIFIED TECHNICIANS Batteries replacement only must be performed by authorized technical service...

Страница 29: ...on service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out o...

Страница 30: ...aintenance Bypass Switch MBS 9 Ventilation grid Power Stage 5 Intelligent port 10 Ventilation grid ISOTX 11 MBS safety plate cover IMPORTANT In case of using an optional ISOTX maximum output of the sy...

Страница 31: ...battery Voltage Voltaje DC Apagado 214VDC 0 30 load 204VDC 30 70 load 192VDC load 70 12V 7AH x 20 pcs 20pcs x 1 240VDC 12V 9AH x 20 pcs 20pcs x 1 240VDC 12V 9AH x 40 pcs 20pcs x 2 240VDC 12V 9AH x 40...

Страница 32: ...n activated El modo bypass se anula automaticamente cuando se activa funci n CF Note 5 If external ISOTX module is used total max power is reduced in 7 Si se usa m dulo ISOTX la potencia final m x ser...

Страница 33: ...INDEX USER MANUAL OPTIMA T09W 6K 10K www xmart ups com VER 1801 25 WP ENG 33 NOTAS...

Страница 34: ......

Страница 35: ......

Страница 36: ...th St Doral FL 33172 USA sales xmart ups com EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain sales xmart ups com Latin America Headquarters Zona Ind San Vicente II C F A11 Maracay V...

Отзывы: