background image

3  Operation 

The XPPS module is very simple to use. In most cases, all that 

is needed is to connect the XPPS to AC power, and connect the 
preamplifier cables, being mindful of connector and cable current 
ratings. For best results, it may be necessary to also connect the ground 
strap to the associated signal processing electronics in order to 
eliminate ground loop noise. Prior to connecting the AC power, it is 
necessary to select the proper input voltage on the AC power input 
module on the rear of the unit; see below for instructions. In most 
cases, the voltage will be set properly prior to shipment. 

3.1  Connector Current Ratings 

Note that the XPPS front-panel DB9 connectors are rated at 2 

Amperes per pin.  As a rule of thumb, each connector should carry no 
more than 1.5 Amperes on any voltage, no more than 3 Amperes total.  
Note: It is always safest to split the load between all four DB9 
connectors. 

 

Current per 

Voltage 

Total 

Current 

Recommendation 

< 1.5 A 

< 3.0 A 

Use one or more DB9 connectors 

< 3.0 A 

< 6.0 A 

Use two or more DB9 connectors 

< 6.0 A 

< 12.0 A 

Use three or more DB9 connectors 

> 6.0 A 

> 12.0 A 

Use all four DB9 connectors 

 
For example, consider a 26-element detector system that 

draws 100 mA on +/-12 V and 50 mA on +/-24 V.  The current 
required at +/-12V is 2.6 A, and the current required at +/-24 V is 1.3 
A.  The total current is 3.9 A.  At a minimum, two DB9 connections 
must be made, however, the best cabling solution would use all four 
DB9 connections. 

3.2  Preamplifier Connector Pinout 

The female DB9 connectors on the XPPS conform to the 

standard pinout for detector preamplifier power connections: 

 

Pin 

Description 

1 and 2 

Ground 

+12V 

-24V 

+24V 

-12V 

3, 5 and 8 

Unused 

 

 

Отзывы: