Default Settings
B–4
975-0385-01-01
Custom Battery Menu
AC Menu
Item
Default Setting
a
a.Custom battery default settings are based on the Flooded battery default settings.
The Gel and AGM default settings are provided here for reference only.
Range
Step
Size
24 V
48 V
24 V
48 V
Eqlz Support
Enabled
Enabled
Enabled, Disabled
n/a
Eqlz Voltage
32.0V
64.0V
27.0–32.0V 54.0–64.0V
0.1
Bulk Voltage
28.8V
28.4V (Gel)
28.6V (AGM)
57.6V
56.8V (Gel)
57.2V (AGM)
20.0–32.0V 40.0–64.0V
0.1
Absorb
Voltage
28.8V
28.4V (Gel)
28.6V (AGM)
57.6V
56.8V (Gel)
57.2V (AGM)
20.0–32.0V 40.0–64.0V
0.1
Float Voltage
27V
27.6V (Gel)
26.8V (AGM)
54.0V
55.2V (Gel)
53.6V (AGM)
20.0–32.0V 40.0–64.0V
0.1
Batt Temp
Comp
54mV/C
(Flooded, Gel)
42mV/C (AGM)
108mV/C
(Flooded, Gel)
84mV/C (AGM)
0–90mV/C
0–180mV/C 1
Item
Default Setting
Range
Step Size
24 V
48 V
24 V
48 V
AC Priority
AC1
AC1, AC2
n/a
AC1 Breaker
56A
3–60A
1
AC1 Lo Volt
202V
156–220V
1
AC1 Hi Volt
260V
240–280V
1
AC1 Lo Freq
45Hz
40–49Hz
40–48Hz
1
AC1 Hi Freq
55Hz
52–68Hz
1
AC2 Breaker
56A
3–60A
1
AC2 Lo Volt
160V
202V
156–220V
1
AC2 Hi Volt
264V
240–280V
1
AC2 Lo Freq
45Hz
40–49Hz
40–48Hz
1
AC2 Hi Freq
55Hz
52–68Hz
1
Содержание XW4024-230-50