Multi-Unit Config Menu
975-0385-01-01
3–23
Multi-Unit Config Menu
The Multi-Unit Config menu configures the XW Inverter/Charger to operate as a
part of a multi-unit installation.
When installing a multi-unit system, each setting on the Multi-Unit Config menu
(except for “Dev Name”) must be configured for each XW Inverter/Charger in the
system. The Multi-Unit Config settings should be configured in the following
order:
•
Dev Number
•
Inverter Mode
•
Connections.
Setting the Device Name
The “Dev Name” setting allows you to customize the name of the XW Inverter/
Charger as it is displayed on other screens and menus.
The characters available are:
•
A to Z
•
a to z
•
0 to 9
•
space.
Important:
Accessing this menu automatically places the XW Inverter/Charger in
Standby mode. When entering the Multi-Unit Config menu, the unit also identifies itself
by flashing all front panel lights. After exiting the Multi-Unit Config menu, the XW
Inverter/Charger returns to Operating mode and the front panel lights stop flashing.
Table 3-9
Multi-Unit Config menu
Item
Description
Default
Range
Dev Name
Allows customization of the default device name. This
setting is optional and does not affect operation. See
“Setting the Device Name” on page 3–23.
n/a
n/a
Dev Number
Allows setting of a unique unit number in a multiple-unit
system. See “Setting the Device Number” on page 3–24.
00
00–31
Inverter Mode
For a multi-unit single-phase system to operate, one XW
Inverter/Charger must be configured to “1Ph Master”
and the rest as “1Ph Slave,” otherwise a system-wide
fault is asserted.
For three-phase systems, one unit must be configured as
the master for each line: 3PhL1Master, 3PhL2Master,
and 3PhL3Master. Additional units on each phase must
be configured as “slave” units: 3PhL1Slave, for
example.
1PhMaster
For single-phase, three-
wire models: 1Ph
Master, 1Ph Slave. For
three-phase systems, see
“Three-Phase
Configuration” on
page 3–25.
Connections
Select to display the Connections menu. See
“Connections Menu” on page 3–27.
n/a