Troubleshooting
4–18
975-0240-01-01
Table 4-5 provides descriptions of the fault messages and solutions. If you are
unable to resolve the problem after referring to this table, contact your dealer or
Customer Service.
Table 4-5
Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution
F1
AC Output Under
Voltage
Escalating
Auto Fault.
Must occur 3
times in 2
minutes before
becoming a
manual fault.
AC under-voltage
shutdown at 108 V. The
inverter has shut down to
protect the loads.
Clear the fault and attempt restart. If
problem persists, call customer
service.
F2
AC Output Over
Voltage
Escalating
Auto Fault.
Must occur 3
times in 30
seconds before
becoming a
manual fault.
AC over-voltage
shutdown at 135 V. The
inverter has shut down to
protect the loads.
Clear the fault and attempt restart. If
problem persists, call customer
service.
F3
AC1 Input L1
Under Voltage
Automatic
AC1 under-voltage
shutdown at the AC1 Lo
Volt setting.
Fault clears when voltage rises
above the AC1 Lo Volt setting. If
fault persists, check AC input
voltage. Check and adjust AC input
low voltage setting.
F4
AC1 Input L1 Over
Voltage
Automatic
AC1 over-voltage
shutdown at the AC1 Hi
Volt setting.
Fault clears when voltage falls
below the AC1 Hi Volt setting. If
fault persists, check AC input
voltage. Check and adjust AC input
high voltage setting.
F5
AC1 Input L1
Under Frequency
Automatic
AC1 under-frequency
shutdown at AC1 Lo
Freq setting.
Fault clears when frequency rises
above the AC1 Lo Freq setting. If
fault persists, check AC input
frequency. Check and adjust AC
input low frequency setting.
F6
AC1 Input L1 Over
Frequency
Automatic
AC1 over-frequency
shutdown at the AC1 Hi
Freq setting.
Fault clears when frequency falls
below the AC1 Hi Freq setting. If
fault persists, check AC input
frequency. Check and adjust AC
input high frequency setting.
F7
AC1 Input L2
Under Voltage
Automatic
AC1 under-voltage
shutdown at the AC1 Lo
Volt setting.
Fault clears when voltage rises
above the AC1 Lo Volt setting. If
fault persists, check AC input
voltage. Check and adjust AC input
low voltage setting.