Installation
Load Connection
46
Operating Manual for XHR Series Power Supply
Radial Power Distribution Method
To connect distributed loads, we
recommend that you use radial power distribution. With this method, you connect
power to each load individually from a single pair of terminals designated as the
positive and negative distribution terminals. These terminals may be the power
supply output terminals, the terminals of one of the loads, or a distinct set of
terminals especially established for distribution use. Connect the sense leads to these
terminals to compensate for losses and minimize the effect of one load upon another.
Figure 2.8
and
Figure 2.9
show recommended load and sensing connections for
multiple loads. Local sense lines shown are default J2 connections. Refer to
Using
Remote Sensing
for how to ground the sense line shield.
Figure 2.8
Multiple Loads with Local Sensing
TM-XROP-01XN.book Page 46 Monday, March 22, 2004 4:10 PM