Accessing Charger Information
Table 9
Interpreting Fault and Warning Indicators
Fault or Warning
Condition
Temp
Fan
AC
Battery
Fuse
Charger
Remote
Fault
Solution
AC input out of range
fault (<85 V or >265 V)
•
Check AC connections. Change to a more stable AC
power source and check that the voltage and voltage
frequency are within acceptable operating range. See
“Specifications” on page 54.
High Battery Temp fault
(>70°C)
•
Check the batteries. Do not charge a battery that is
rated other than 12 V nominal for all 12-volt chargers
or 24 V nominal for all 24-volt chargers. Check that
the battery type and temperature settings match the
actual battery and its conditions.
•
Disconnect or turn off other charging sources such as
an alternator or the charger on a generator with an
electric start.
•
Allow the battery (or batteries) to cool to normal
operating temperature. See “Specifications” on page