ACS Configuration Considerations
34
Prosine 2.5/3.0 Installation & Operation Guide
The voltage range for these alarms and cutoffs is generally set at the factory at the absolute minimum
and maximum, as shown in the illustration above for 12-volt systems. Example: Lo Cutoff = 10.0V, Hi
Cutoff = 16.0V, Range = 10.0 to 16.0 volts DC. The table below illustrates the factory settings and the
min–max range for both 12-volt and 24-volt systems.
Charger Configuration
The ACS Charger menu displays the current status of the charger and enables you to begin an
equalization charge, or to override the current charger status and force the charger into Float or
Equalization mode.
Override Charger Operating Mode
The charger will not begin an equalization charge until it has
completed a Bulk or Absorption charge. It may be desirable to force an equalization charge in some
instances. Forcing the charger into Float or Equalization mode is usually performed only during an
installation, and should not be lightly considered. Consult your installer or call Xantrex Customer
Service before attempting to override the charger mode. Overriding the charger operating mode is an
installer-configuration item. The menu procedure is illustrated below.
Enter “Installer Mode, and then:
Equalization Request
For some batteries, equalization is a regular maintenance activity; for
others, equalization is damaging. Read
“Section 6: Multistage Charging”
) before attempting
to initiate an equalization charge. Inappropriate equalization charging can ruin your batteries. An
equalization request is a user-configuration item: press
ENTER
at the menu and follow the prompts
shown below to initiate an equalization request. When you press
ENTER
at the YES prompt,
equalization will begin immediately if the batteries are fully charged, and AC power is available.
Since equalization voltage is usually above the range of the High Voltage Alarm, an audible alarm will
sound briefly when it is enabled. The Faults and Charger LEDs will also flash as a visual alarm. This
High and Low Voltage Alarms and Cutoffs
ALARM OR CUTOFF
12-VOLT MIN-
MAX RANGE
Factory
Default
24-VOLT MIN-
MAX RANGE
Factory
Default
LO ALARM
10.0V - 12.0V
10.5V
20.0V - 24.0V
21.0V
HI ALARM
14.0V - 16.0V
15.5V
28.0V - 32.0V
31.0V
LO CUTOFF
10.0V - 12.0V
10.0V
20.0V -24.0V
10.0V
HI CUTOFF
14.0V - 16.0V
16.0V
28.0V - 32.0V
16.0V
OVERRIDE CHARGER
OPERATING MODE
SELECT FROM:
CHARGER
ENTER
FORCE CHARGER TO
FLOAT CHARGE
ENTER
FORCE CHARGER TO
EQUALIZE CHARGE
ENTER
Содержание Prosine PS2.5 and
Страница 1: ...Xantrex ProsineTM 2 5 and 3 0 Inverter Chargers Installation and Operation Guide PS2 5 PS3 0...
Страница 2: ...ProsineTM PS2 5 Inverter Charger PS3 0 Inverter Charger Installation and Operation Guide...
Страница 9: ...vi Prosine 2 5 3 0 Installation Operation Guide Figure 1 Inverter Charger Components...
Страница 13: ...Return Procedure x Prosine 2 5 3 0 Installation Operation Guide...
Страница 21: ...Inverter Features 4 Prosine 2 5 3 0 Installation Operation Guide...
Страница 41: ...Battery Temperature Sensor 24 Prosine 2 5 3 0 Installation Operation Guide...
Страница 75: ...Operating Limits for Inverter Operation 58 Prosine 2 5 3 0 Installation Operation Guide...
Страница 83: ...Operating Limits for Charger Operation 66 Prosine 2 5 3 0 Installation Operation Guide...
Страница 95: ...Cabling Hook up Configurations 78 Prosine 2 5 3 0 Installation Operation Guide...
Страница 98: ...Prosine 2 5 3 0 Installation Operation Guide 81 Appendix A Specifications Prosine 2 5 3 0 Chassis Dimensions...
Страница 99: ...82 Prosine 2 5 3 0 Installation Operation Guide Prosine 2 5 3 0 Chassis Dimensions with Brackets...
Страница 101: ...84 Prosine 2 5 3 0 Installation Operation Guide...
Страница 111: ...Error Code Table 94 Prosine 2 5 3 0 Installation Operation Guide...