Specifications
975-0125-02-01
A–3
Main Charger Specifications
All charging specifications are at nominal conditions: ambient temperature of 77
°F (25 °C), 120 VAC, 60 Hz input, unless otherwise specified.
Table A-2
Main Charger Specifications
Charging method
•
Three-stage charge (Bulk, Absorption, Float)
•
Two-stage charge (Bulk, Absorption)
The default charging method is three-stage.
Without a battery temperature
sensor
Three settings with the following temperature
values:
•
Cool 50 °F (10 °C)
•
Warm 77 °F (25 °C)
•
Hot 104 °F (40 °C)
The default value for this setting is Hot, and it can
only be changed by a dealer, factory, or service
center.
With a battery temperature
sensor
The temperature compensation coefficients on a
12 volt battery are as follows:
•
Flooded: 27 mV × (25 °C – BTS °C)
•
Gel: 27 mV × (25 °C – BTS °C)
•
AGM: 21 mV × (25 °C – BTS °C)
Equalization cycle
Yes, manual via System Control Panel
Number of independent battery
banks
1
Battery bank size settings
50 – 2000 Ah
Battery type settings
Flooded, AGM, Gel, Custom
Power factor corrected charging Yes
AC input voltage
90 – 135 VAC
AC input frequency
60 Hz nominal, 55 – 65 Hz operating range
Minimum battery voltage
3.0 VDC
Maximum DC output voltage
16.0 VDC
Charger efficiency
≥
85%
Input power factor at full
charge rate
> 0.95
Maximum charge current
100 A
Содержание MS2000
Страница 1: ...MS2000 Sine Wave Inverter Charger Operation Guide MS2000 ...
Страница 2: ......
Страница 3: ...MS2000 Sine Wave Inverter Charger Operation Guide ...
Страница 8: ...vi ...
Страница 18: ...xvi ...
Страница 28: ...Introduction 1 10 975 0125 02 01 Figure 1 5 DC Grounding Completed ...
Страница 111: ...C Terminology This section provides a glossary of terms and a listing of abbreviations used in this guide ...
Страница 124: ...IX 4 ...
Страница 125: ......