Wiring the Inverter
3–8
975-0253-01-01
5. On the female terminal, connect the protective earth wire to the terminal
marked with the
symbol. See Figure 3-6.
6. Connect the neutral conductor to the terminal marked with 1.
7. Connect the Active conductor to the terminal marked with 2.
Terminal 3 is not used.
8. After ensuring all the wires are tightened in their terminals, screw the shell
onto the female terminal.
9. Replace the remaining components of the female cable connector, ensuring a
tight seal.
10. Tighten the pressing screw.
To connect the AC connector to the GT Inverter:
1. Line up the notch on the female AC cable connector with the connector on the
GT Inverter.
2. Insert the AC cable connector into the connector on the GT Inverter.
3. Secure the connector by turning the outer ring.
Figure 3-5
AC Connector (Female)
Figure 3-6
AC Connector Terminals
Female terminal
Shell
Seal
Pinch ring
Pressing screw
Outer ring
Notch
AC connector terminals
(see Figure 3-6)
Protective Earth
wire
Not used
Neutral wire
Active Phase
L wire
www.xantrex.com.ua
Содержание GT 2.5-DE, GT 3.8-DE, GT 2.8-S
Страница 2: ...www xantrex com ua ...
Страница 8: ...vi www xantrex com ua ...
Страница 13: ...Contents 975 0253 01 01 xi Warranty and Return Information WA 1 Index IX 1 www xantrex com ua ...
Страница 14: ...Contents xii 975 0253 01 01 www xantrex com ua ...
Страница 16: ...xiv www xantrex com ua ...
Страница 18: ...xvi www xantrex com ua ...
Страница 56: ...Wiring the Inverter 3 18 975 0253 01 01 www xantrex com ua ...
Страница 60: ...4 4 www xantrex com ua ...
Страница 78: ...Maintenance and Troubleshooting 6 6 975 0253 01 01 www xantrex com ua ...
Страница 91: ...www xantrex com ua ...