12
©2001 Xantrex Technology Inc.
Generator Wiring
(continued)
Wiring Onan-Type Generators
In this system, RY8 duplicates the START position and relay RY7
duplicates the STOP position. Some generators use a similar system with
two push-button switches, one to start and one to stop the generator.
Connect the COM contact of RY7 to one of the STOP switch contacts of
the generator.
Connect the COM contact of RY7 to the COM contact of RY8.
Connect the N.O. contact of RY7 to the other STOP switch contact of
the generator.
Connect the N.O. terminal of RY8 to the START switch contact.
Select
GLOWSTOP
from the SWRCs
SET RY7 FUNCTION
menu item
(found under the
GEN STARTING DETAILS (13)
menu heading).
GEN START MODULE
RY7
STOP SWITCH
CONTACTS
ONAN 3-WIRE TYPE GENERATOR
To Inverter’s
GEN Connector
COM
N.O.
N.C.
RY8
COM
N.O.
N.C.
START
SWITCH
CONTACTS
INTERNAL
FUSE
INTERNAL
FUSE
2.0 INSTALLATION
Figure 10
Onan-Type Start Connections