Operating During Transition Between Grid Mode and Battery Mode
72
Freedom XC PRO Owner's Guide
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Output Frequency
07
60
60
50
After changing the output frequency setting, turn the unit off and
then on again, in order for the change to take effect.
Output Voltage
08
120
120
110
108
Inverter Output Power
Limit (Freedom XC PRO
2000)
09
2
.
0
0
.
1
to
2
.
0
The wattage setting value can be adjusted by 100-watt
increments. Use with Inverter Output Power Limit Timer especially
when pairing with a lithium ion battery. 0.1 is equivalent to 100
watts.
Inverter Output Power
Limit (Freedom XC PRO
3000)
09
3
.
0
0
.
1
to
3
.
0
The wattage setting value can be adjusted by 100-watt
increments. Use with Inverter Output Power Limit Timer especially
when pairing with a lithium ion battery. 0.1 is equivalent to 100
watts.
Inverter Output Power
Limit Timer
10
300
1
to
300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-second increments. When the range is from 20 to
300, the timer setting value can be adjusted by 10-second
increments.
Use with Inverter Output Power especially when pairing with a
lithium ion battery. The timer is automatically disabled if the
maximum Inverter Output Power limit is selected.