Side Panel
975-0767-01-01
23
Side Panel
1
2
2
1
3
Figure 4 Side Panel
WARNING
ELECTRICAL SHOCK HAZARD
n
Use a torque screwdriver to tighten the captive nut panel
screw to 5 in-lb (0.56 N-m) torque to ensure a proper
ground connection and a required tool access to the wiring
compartment.
n
Use a torque screwdriver to tighten the bolt on the DC
ground lug to a torque of 23 in-lb (2.6 N-m) of force.
n
Apply an anti-corrosion compound to the copper wire prior
to connecting to the DC ground lug.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
Item
Description
1
Captive nut panel screw
holds the wiring compartment
cover in place. See WARNING above.
2
Wiring compartment cover
protects the wiring
compartment from debris and keeps the cables secure.
Using the captive nut panel screw, the cover can be
opened and lifted out during wiring. See WARNING on the
left.
3
Grounding lug
provides a ground path for the Freedom X
1200 chassis to the DC system ground. See WARNING.
Table 3 Side Panel Features