Configuring the Freedom SW using the SCP
•
If using an automatic generator starting system, it is
recommended to set the Xanbus AGS voltage trigger
setting higher than the Freedom SW
Low Batt Cut Out
voltage.
•
Although not recommended, if using an automatic
generator starting system with the start trigger set to the
same voltage as the LBCO voltage, do not set the
LBCO
Delay
to less than the amount of time it takes the
generator to start and connect.
Otherwise – in both of the scenarios above – inverter output
turns off before the generator automatically starts, causing the
battery voltage to recover slightly. This may then stop the
Xanbus AGS from starting the generator or result in the
Freedom SW cycling on and off multiple times before the
generator automatically starts.