
97-0019-01-01
97
Troubleshooting
F69
External Sync
Failed
Automatic
When Series
stacking— the
Stacking cable is not
installed.
Install the Stacking cable to connect
the two inverter/chargers.
F70
Unique Dev#
Needed
Automatic When
stacking
(Series
or Parallel)—if two
units have the same
Device Number.
Change the Device Number of one
unit. See “Setting the Device Number”
on page 71.
F71
Too Many
Masters
Automatic When
stacking
(Series
or Parallel)—if two
units are configured as
Master units.
Change one unit to a Slave unit. See
Stack Mode under “Stacking
Configuration Menu” on page 68 in
Table 17.
F73
Transformer
Temp
unreadable
Automatic
Temperature sensor is
damaged.
Service required.
Table 3
Detected Fault Messages
Fault
Number
Message
Fault Type
Cause
Solution
FSW Owners Guide.book Page 97 Tuesday, August 7, 2018 9:03 AM
Содержание Freedom SW Series
Страница 2: ...FSW Owners Guide book Page ii Tuesday August 7 2018 9 03 AM...
Страница 14: ...FSW Owners Guide book Page iv Tuesday August 7 2018 9 03 AM...
Страница 30: ...FSW Owners Guide book Page 16 Tuesday August 7 2018 9 03 AM...
Страница 116: ...FSW Owners Guide book Page 102 Tuesday August 7 2018 9 03 AM...
Страница 121: ...FSW Owners Guide book Page i Tuesday August 7 2018 9 03 AM...