975-0546-01-01
37
Installing the Inverter/Charger
This
g
u
id
e for
u
se by qu
alifi
ed installers only.
Step 7: Performing Checks Prior to Initial Start-Up
Before testing your installation, ensure these conditions are met:
❐
Chassis and AC grounds are properly installed.
❐
AC input connections and AC output connections are wired correctly
on the terminal block and not reversed.
❐
Positive (+) battery cable is connected to the positive (+) battery
terminal through the DC fuse and disconnect switch or DC circuit
breaker.
❐
Negative (–) battery cable is connected to the negative (–) battery
terminal.
❐
Battery voltage is within the proper range for this unit
(10–16 volts DC).
❐
DC disconnect switch or breaker is turned off.
❐
AC input and output breakers are turned off.
❐
All connections are tight.