Freedom e-GEN System User Guide

975-0791-01-01 Rev F

Sep 2019

Copyright © 2019 Xantrex LLC. All Rights Reserved.

All trademarks are owned by Xantrex LLC and its affiliates.

3

11

BMS LED Indicator

The e-GEN Xantrex BMS has an LED indicator integrated into the Power button on the unit
itself. In some cases, there are also optional remote LED indicators – one to indicate power
(On/Off/Alarm) status and one to indicate low battery status. Please refer to your specific
installation to check which LEDs, if any, you have available in your system.

Power On/Off/Alarm

– This LED indicator is integrated into the Power button on

the BMS unit or is installed remotely as an option.

l

The LED is off when the BMS is turned off and battery power is disabled.

l

The LED is on when the BMS is on and battery power is enabled.

l

The LED flashes rapidly when BMS is in alarm state and battery power is
disabled.

12

Power and Environmental Specifications

NOTE

: Specifications are subject to change without prior notice.

The specifications listed here are for the Freedom e-GEN System. Certain operating
conditions apply. For complete specifications, refer to each device’s datasheet and
Owner’s Guide.

Electrical
Overview

Energy Storage Capacity

600 Ah or 450 Ah

Nominal System DC Voltage

12.8VDC

Nominal System AC Voltage

120VAC @60Hz

System AC Output Power Rating

3000W up to 40 °C (104 °F)

Lithium-ion
Battery
Voltage
versus SoC

Battery State

Battery Voltage

State-of-Charge (SoC)

Fully Charged

14.6V – 13.6V

100%

Nominal Operation

14.6V – 12.2V

100% – 12%

Float Voltage

13.4V

100% – 80%

Low Battery Warning

12.2V

12%

Reserve Shutdown

12.0V

10%

Low Battery Shutdown

11.6V

<3%

Temperature

Charging range*

0 – 45 °C (32 – 113 °F)

Discharging range*

-20 – 55 °C (-4 – 131 °F)

* Staying within the recommended ambient temperature range will yield optimal system performance. For maximum
temperature specifications, refer to each device's datasheet and Owner's Guide.

Storage

Recommended temperature and
humidity

15 to 35°C (59 to 95°F)

45 to 75

RH

Temperature range

< 1 Month, -20 to 35°C (-4 to 95°F)

< 3 Months, -10 to 30°C (14 to 86°F)

For long term storage, see the

Battery

Storage Guide (doc number 975-1005-01-
01)

.

Battery
Disposal

At the end of the battery’s useful life, proper disposal is required. Do not dispose the battery
with ordinary household waste. Refer to your local codes for proper disposal of lithium-ion
batteries.

Full Vlt

Full Voltage

Set this to the maximum per-cell voltage your battery reaches at the end-
of-charge. This will be used to synchronize the SoC LCD Display’s
100% reading when the battery reaches this voltage level.

Typically, this value is 3.55 V per cell. So, a 12 V (4 cell) battery is 4 x
3.55 = 14.2 V. When the battery reaches this voltage at the end of a
charge cycle, the SoC value will reset to 100%.

NOTE

: If you notice that your SoC LCD Display's value never reaches 100% at the

end of a charge cycle, you may need to slightly lower the Full Vlt value to what the
voltage reading is on the LCD Display at the moment, when the charger turns off.
This value must be higher than the resting voltage of the battery since the charger’s
end voltage is higher than its resting voltage. The typical value range should be
between 14.0 and 14.4 V.

Min SoC

Minimal State-of-

Charge

This percentage value sets the Empty Battery level, also known as
Reserve Capacity, so the user can utilize the BAT Gauge reading and
not completely deplete the battery thus, preserving its lifecycles. For
example, if this value is set to 10%, then the BAT Gauge will report 0%
when there is still 10% reserve SoC. If you desire to use your battery to
its full capacity and/or want the BAT Gauge to reflect true SoC, then set
this value to zero.

In addition, when RVC Mode is enabled, the BMS will turn off battery
power when SoC reaches this preset level (assuming it comes before
battery voltage reaches RVC level), typically 3.00VPC. This allows the
Xantrex Reserve feature to act on both voltage trigger and SoC level
trigger, whichever comes first.

AGSR Lvl 

Automatic

Generator

Start/Restart level

This percentage value determines the minimal Bat Gauge level at which
the AGS/R circuit is triggered. AGS/R circuit triggers on voltage set to
3.05 V per cell, or the Low Bat level, whichever comes first, hence
allowing flexible control of the generator starting point. 

Temp Unit

Temperature Units

Set this to Fahrenheit (°F) or Celsius (°C). 

Charge Eff

Charging Efficiency

This percentage value slows down the rate of SoC climb during the
charge to compensate for battery losses during the discharge cycle. The
recommended setting is 98%. In applications with high discharge rates,
energy losses are more pronounced, so this value must be set lower to
accurately report SoC and BAT Gauge values during partial
charges.This setting must be tuned experimentally for best accuracy.
Ideal setting will cause SoC to reach 100% at approximately the same
time as the charger is finishing up the full charge. 

Dead Zone

Due to thermal drift in Hall Effect sensors when temperature fluctuations
are wide and fast, the BMS might report non-zero current reading when
no current is present. The Dead Zone value allows ignoring small
current readings when they are likely false (such as, when small reading
fluctuates between zero and non-zero values). Default value of 0.3A is
recommended for best zero-point stability. 

Idle Load

Shown as mA

This setting represents the constant idle load current powering the BMS
system. This can be measured with a digital multi-meter in DC
amperage mode in series with the BMS’s negative reference wire.
Allowed range is 0 – 200 mA. Since the idle current is usually too low to
register by internal hall-effect sensor but still affects SoC reading over
long time periods when the battery sits idle, setting this value allows for
a better long-term accuracy of the SoC counter.

Alarm

Alarm function

Turns ON or OFF an Alarm function, which drives the internal buzzer as
well as the AUXOUT2 external relay circuit when the BMS is in Alarm
state.

RVC

Reserve voltage

cutoff function

Default setting STD (Standard) would turn off the battery while leaving
reserve charge, which can be accessed by pressing the Reset button.
When set to EXT (Extended), the amount of reserve charge is increased
on voltage-based triggers.