Specifications of the DR Inverter
975-0012-01-02 Rev A
A–3
DC Input Voltage
(nominal)
c
12.6 Vdc
12.6 Vdc
25.2 Vdc
25.2 Vdc
25.2 Vdc
DC Input Voltage
Range
10.8 to 15.5 Vdc 10.8 to 15.5 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc 21.6 to 31.0 Vdc
Auto Low Battery
Protection enabled
11 V
11 V
22 V
22 V
22 V
DC Charger Rate
(Adjustable)
0 to 70 amps
0 to 120 amps
0 to 35 amps
0 to 70 amps
0 to 70 amps
Common Specifications:
Voltage Regulation
(maximum)
± 5%
Voltage Regulation
(Typical)
±2. 5%
Waveform
modified sine wave
Load Power Factor
(allowed)
0.5 to 1.0 (leading or lagging)
Adjustable Load
Sensing Range
5 watts minimum to 100 watts maximum
Series Operation
Yes
Force Air Cooling Variable speed fan
Automatic Transfer
Relay
30 amps
Number of
Charging Profiles
10
Three-stage
Charging
Yes (float, absorption, bulk)
Temperature Comp
Probe (BTS)
optional
Remote Control
(RC8)
d
optional
a.Specifications subject to change without notice.
b.This is the minimum AC current required to obtain full pass-through and maximum battery charging.
c.Product may not meet voltage regulation specifications at other than "Input Nominal" at full-rated load.
d.Also compatible with the RC4.
Table A-1
Electrical Specifications for the DR Inverter/Charger
a
- 120 Vac/60 Hz Models
Model
DR1512
DR2412
DR1524
DR2424
DR3624
Содержание DR1512E
Страница 2: ......
Страница 3: ...DR Inverter Charger Installation and Operation Manual...
Страница 10: ...viii...
Страница 18: ...xvi...
Страница 32: ...Installation 2 8 975 0012 01 02 Rev A Figure 2 3 On Grid Configuration with Renewable Energy Sources...
Страница 38: ...Installation 2 14 975 0012 01 02 Rev A Figure 2 9 DC Grounding...
Страница 57: ...3 Operation Chapter 3 Operation contains information about how to operate the DR Inverter Charger...
Страница 82: ...4 6...
Страница 90: ...A 8...
Страница 108: ...B 18...
Страница 120: ...IX 2...
Страница 121: ......