Battery Information
B–14
975-0012-01-02 Rev A
Temperature compensation is based on battery type — 5 mv/cell for lead acid type
batteries and 2 mv/cell for alkaline type batteries (NiCad or NiFe). The
temperature compensation calculations are derived from Table B-5.
Table B-4
Variances in Charging Voltage based on Battery Temperature
Temperature
(around the BTS)
12-volt units
24-volt units
48-volt units
Celsius
Fahrenheit
Lead Acid
(6 cells)
NiCad
(10 cells)
Lead Acid
(12 cells)
NiCad
(20 cells)
Lead Acid
(24 cells)
NiCad
(40 cells)
60
140
-1.05
-0.70
-2.10
-1.40
-4.20
-2.80
55
131
-0.90
-0.60
-1.80
-1.20
-3.60
-2.40
50
122
-0.75
-0.50
-1.50
-1.00
-3.00
-2.00
45
113
-0.60
-0.40
-1.20
-0.80
-2.40
-1.60
40
104
-0.45
-0.30
-0.90
-0.60
-1.80
-1.20
35
95
-0.30
-0.20
-0.60
-0.40
-1.20
-0.80
30
86
-0.15
-0.10
-0.30
-0.20
-0.60
-0.40
25
77
0.00
0.00
0.00
0.00
0.00
0.00
20
68
0.15
0.10
0.30
0.20
0.60
0.40
15
59
0.30
0.20
0.60
0.40
1.20
0.80
10
50
0.45
0.30
0.90
0.60
1.80
1.20
5
41
0.90
0.60
1.20
0.80
2.40
1.60
0
32
0.75
0.50
1.50
1.00
3.00
2.00
-5
23
0.90
0.60
1.80
1.20
3.60
2.40
-10
14
1.05
1.20
2.10
1.40
4.20
2.80
-15
5
1.20
0.80
2.40
1.60
4.80
3.20
-20
-4
1.35
1.40
2.70
1.80
5.40
3.60
-25
-13
1.50
1.00
3.00
2.00
6.00
4.00
-30
-22
1.65
1.10
3.30
2.20
6.60
4.40
-35
-31
1.80
1.20
3.60
2.40
7.20
4.80
-40
-40
1.95
1.30
3.90
2.60
7.80
5.20
Table B-5
Temperature Compensation Calculation
Battery Type
24-volt Systems
48-volt Systems
Lead Acid
0.060 volts (60 mV) per
degree Celsius
0.120 Volts (120 mV) per degree
Celsius
NiCad
0.040 volts (40 mV) per
degree Celsius
0.080 volts (80 mV) per degree
Celsius
Important:
If the battery temperature is allowed to fall to extremely cold
temperatures, the inverter with a BTS may not be able to properly recharge cold
batteries due to maximum voltage limits of the inverter. Ensure the batteries are
protected from extreme temperatures.
Содержание DR1512E
Страница 2: ......
Страница 3: ...DR Inverter Charger Installation and Operation Manual...
Страница 10: ...viii...
Страница 18: ...xvi...
Страница 32: ...Installation 2 8 975 0012 01 02 Rev A Figure 2 3 On Grid Configuration with Renewable Energy Sources...
Страница 38: ...Installation 2 14 975 0012 01 02 Rev A Figure 2 9 DC Grounding...
Страница 57: ...3 Operation Chapter 3 Operation contains information about how to operate the DR Inverter Charger...
Страница 82: ...4 6...
Страница 90: ...A 8...
Страница 108: ...B 18...
Страница 120: ...IX 2...
Страница 121: ......