Basic Installation Procedures
23
Freedom SW-RVC Installation Guide
Disconnect
Devices
Each system requires a method of disconnecting
the AC circuits. If the overcurrent protection device
is a circuit breaker, it will also serve as the
disconnect. If fuses are used, separate AC
disconnect switches will be needed between the
source and the fuses.
Distribution
Panels
Some systems incorporate distribution panels both
ahead of the inverter/charger (the AC source panel)
and between the inverter/charger and the loads (the
AC load panel). The AC source panel includes a
main circuit breaker, which serves as overcurrent
protection for the panel. Additional circuit breakers
serve individual circuits, one of which serves the
inverter/charger.
AC Wiring
Definition
AC wiring includes input wiring (all the wires and
connectors between the AC source and the
inverter/charger input) and output wiring (all the
wires between the inverter/charger and the AC load
panels, circuit breakers, and loads).
Type
The type of wiring required varies according to the
electrical codes or regulations applicable to your
installation. For RV applications, this may be solid
wire in multi-conductor cables, but stranded wire is
required if single conductors are used. All wiring
must be rated 90 °C or higher.