Xtreme Power Conversion Corporation
TX90 6kVA & 10kVA User’s Manual
Page 20
Uninterruptible Power Supply
S
Bypass Voltage is adjusted to narrow range. Selectable to Lo or Hi.
T
Frequency Window is +/-3 Hz. Selectable to ± 1Hz.
U
Inverter output voltage set to 208V. Selectable to 200, 208, 220, 230, 240V. This is the voltage
sent to the output transformer primary. The UPS output voltages depend on what output con-
figuration is chosen. Please refer to the Output Configuration section of this manual.
V
The UPS is operating in “normal mode”. Selectable to ECO, CF50, CF60, and Normal.
W
Output Voltage Adjustment (-1, -2, -3, 0, 1, 2, 3%)