X-TREME TX90 Скачать руководство пользователя страница 13

Xtreme Power Conversion Corporation

TX90 6kVA & 10kVA User’s Manual

Page 13

Uninterruptible Power Supply

L11 NOT USED:

 all systems are single input

N1, L12, G1:

 the terminals for utility input with single input connection

G1:

 the terminal for UPS input ground

N1: 

line 1 (L1) input

L12:

 line 2 (L2) input

G2, N22, L22, N21, L23, L21:

 the terminals for UPS output, see below output options for configuration details

G2:

 the terminal for UPS output ground

Remarks:

1. 

The maximum current for each terminal is 30 Amps for 6 kVA, 50 Amps for 10 kVA.

2. 

The UPS is always a Single Input configuration. The Dual Input configuration is not used. The AC source can 

be 208V or 240V landed to the L12 and N1 terminals.

3.  Use No. 6 AWG, 75°C minimum copper wire and 23 lb-in Torque force when connecting to terminal block.

4.  The transformer has two input voltage options, 208V and 240V. If the input is configured at 208V but the 

actual input is 240V, then the output voltages will boost up 15%.

Input Configuration

208V input applications:

 208V input with a 120/240V output is the default for these systems. This means the in

-

verter output is programmed to 208V and the output transformer primary tap is set to the 208V setting. These are 

the default settings for this system. Please refer to output Option 1 in this section.

240V input applications:

 If the input voltage is 240V, the following steps must be performed to obtain a 120/240V 

output with a 240V input. 

1. 

With no AC applied to the unit, change the transformer primary tap from 208V default setting to 240V 

shown below. Access to tap settings is gained by removing the side covers.

      

 

 

 

 TX90-6K Input Taps 

 

              TX90-10K Input Tap Board

2. 

The UPS inverter output voltage must also be programmed to 240V. Refer to the Changing the UPS Default 

Settings section for more details. Option 1 below provides a 120/240V output with a 240V input.

Move red 

wire to here 

when there is 

a 240V input

Tap shown 

on the 208V 

setting

240V tap

Содержание TX90

Страница 1: ...TX90 6kVA 10kVA Online UPS 6kVA 10kVA Models User Installation Manual www xpcc com 2015 Xtreme Power Conversion Corporation All rights reserved Rev 8 27 15...

Страница 2: ...ion And Operation 12 Unpacking 12 Selecting Installation Position 12 TerminalBlockExplanation 12 InputConfiguration 13 OutputConfiguration 14 Start Up in Normal Mode 15 Check Measured Values and Figur...

Страница 3: ...rvice 31 Xtreme Power Conversion Limited Warranty 32 Xtreme Power Conversion Load Protection Policy 33 Appendix A T90 EBP920 EBP940 EBP960 User Guide 36 Introduction To The Rear Panel 37 Installation...

Страница 4: ...ny UPS Install the UPS away from objects that give off excessive heat and areas that are excessively wet If liquids are spilled onto the UPS or foreign objects dropped into the unit the warranty will...

Страница 5: ...E INSTRUCTIONS CAUTION Do not dispose of batteries in a fire The batteries may explode CAUTION Do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic CA...

Страница 6: ...unit become overheated the internal thermal switch will detect the heat and switch to bypass mode and vice versa The fully digitalized control circuit built into the UPS allows upgrading the functiona...

Страница 7: ...ility is abnormal the batteries will be boosted to provide the DC voltage to the Inverter 5 Internal Battery When AC abnormal it provide the backup power from the batteries 6 Charger the battery charg...

Страница 8: ...specified mode 6 A Blackout Transfer occurred in UPS Output 7 Bypass Input Abnormal UPS fails to transfer to bypass Bypass Abnormal at ECO mode 8 Utility Input Abnormal 9 OFF UPS Shut off 10 LINE OFF...

Страница 9: ...Wrong Procedure to Enter Maintenance Mode 33 Er16 Output Parameters Set Error in Parallel System 34 Er17 ID Numbers are in conflict in Parallel System or ID number error in single unit 35 Er21 Parall...

Страница 10: ...ing green LED indicates that the utility input voltage is outside the acceptable window 4 Green LED indicates that Bypass Input is normal 5 UPS ON Alarm Silence 6 Go to previous page or change the set...

Страница 11: ...optional interface cards for Relay Dry Contact and SNMP These cards may be used simultaneously The software bundled with the UPS is compatible with many operating systems such as Windows 98 2000 ME N...

Страница 12: ...Position Install the UPS in a proper environment to minimize the possibility of damage to the UPS and to extend the life of the UPS Please follow these requirements 1 Keep at least 12 inches clearance...

Страница 13: ...configured at 208V but the actual input is 240V then the output voltages will boost up 15 Input Configuration 208V input applications 208V input with a 120 240V output is the default for these systems...

Страница 14: ...ity output Please note the jumpers between G2 N22 N22 N21 and L22 L21 for this option See below For any other output configurations needed please contact Xtreme Power Tech Support Please refer to the...

Страница 15: ...Utility and Bypass inputs are normal UPS will display first figure A1 and then figure B A1 B The UPS is now in Bypass Mode It will proceed to self test automatically If no abnormal message appears the...

Страница 16: ...e protected Start up in Battery Mode Cold Start Make sure the UPS has at least one string 20 pcs of batteries Push the UPS On switch once for approximately 5 seconds to wake the UPS The buzzer will so...

Страница 17: ...es detected by the UPS use the scroll up and scroll down keys When you scroll down the LCD will display figure C Voltage from Utility Input figure I1 Voltage from Bypass Input figure J Frequency from...

Страница 18: ...ower Conversion Corporation TX90 6kVA 10kVA User s Manual Page 18 Uninterruptible Power Supply K Frequency of Bypass Input L UPS output voltage M UPS output frequency N UPS output load level O Battery...

Страница 19: ...ill display in sequence figure Q1 buzzer figure R Self test figure S Bypass Voltage Windows figure T Output Frequency Synchronization Window figure U Inverter Output Voltage figure V UPS Operation Mod...

Страница 20: ...ectable to 1Hz U Inverter output voltage set to 208V Selectable to 200 208 220 230 240V This is the voltage sent to the output transformer primary The UPS output voltages depend on what output con fig...

Страница 21: ...ndicates the bypass frequency window of the Inverter Output The acceptable setting values are 3 Hz and 1 Hz Figure U indicates the acceptable Inverter Output Voltage Possible values are 200 208 220 23...

Страница 22: ...blem For further help consult your local distributor 3 Press the Off key for five seconds A buzzer will sound twice 4 Turn Off the Utility Input breaker 5 Even if the UPS lock problem is solved now co...

Страница 23: ...enance now 5 When you are done with UPS maintenance put the UPS back into normal working mode as explained previously Then return the CAM switch to INV mode replace the cover The UPS will switch back...

Страница 24: ...uncritical load at the UPS output end If there is any damage to the insulation of the AC power cord please replace it with a new one EPO Remove the short circuit at the EPO terminal Er11 Er33 Remove a...

Страница 25: ...Connect the male connector of the RS 232 cable to the UPS communication port 2 Connect the female connector of the RS 232 cable to a dedicated RS 232 port of the attached computer Software Installati...

Страница 26: ...function will be activated after 6 25 VDC is applied between pin 9 and pin 10 for 5 sec onds The capacity of each relay contact is 40 VDC 25mA Installation Position slot 1 CHA CN7 or slot 2 CHB CN8 Fl...

Страница 27: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA User s Manual Page 27 Uninterruptible Power Supply Interface Card Installation 1 3 2...

Страница 28: ...by qualified personnel only 1 Unscrew the bottom of the front panel as indicated in Step 1 below 2 Remove the front panel as indicated in Step 2 TX90 6K shown above 3 Remove the screw of the battery...

Страница 29: ...Conversion Corporation TX90 6kVA 10kVA User s Manual Page 29 Uninterruptible Power Supply 6 Rotate the battery pack handle 90 degrees as shown in Step 6 7 Remove the battery packs from the UPS as sho...

Страница 30: ...in Weight 265 lbs 340 lbs OPTIONAL Battery quantity and size EBP920 20 12V 9AH EBP940 40 12V 9AH EBP960 60 12V 9AH BATTERY PACKS Dimensions W x D x H 11 4 x 25 4 x 29 5 in Weight EBP920 254 lbs EBP940...

Страница 31: ...will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Autho...

Страница 32: ...the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjecte...

Страница 33: ...the XPC Limited Warranty against certain losses caused by a Power Disturbance for properly connected electronic equipment referred to as the Connected Equipment subject to certain terms and conditions...

Страница 34: ...e Load Protection Policy The following damage is not covered by this Policy 1 Restoration of lost data and reinstallation of software 2 Damage from a cause other than AC power line transients except f...

Страница 35: ...issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment up to the dollar limits stated above XPC reserves t...

Страница 36: ...r poured directly onto the battery bank Similarly we do not warrant any damage to the battery bank if foreign objects are deliber ately or accidentally inserted into the battery bank enclosure The bat...

Страница 37: ...Corporation TX90 6kVA 10kVA User s Manual Page 37 Uninterruptible Power Supply Introduction To The Rear Panel Rear Panel Descriptions T90 EBP920 EBP940 EBP960 Product Label DC Breaker UPS Connector Ba...

Страница 38: ...ect cable o The casters cover kits Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery bank...

Страница 39: ...Xtreme Power Conversion Corporation TX90 6kVA 10kVA User s Manual Page 39 Uninterruptible Power Supply Installation of Casters Cover Installation Instructions...

Страница 40: ...ersion Corporation TX90 6kVA 10kVA User s Manual Page 40 Uninterruptible Power Supply Specifications T90 EBP920 T90 EBP940 T90 EBP960 Dimensions W x D x H Unit 11 4 x 25 4 x 29 5 in Weight Unit 254 lb...

Отзывы: