W-LINK-CAN
Product information
Page 4 of 4 Subject to technical changes
W-LINK-CAN_V1.70_PI_2018-08_EN
4
Connections
WARNING! Danger of death from electric shock and/or fire!
The wiring of the device should be carried out only by a qualified electrician!
Note!
•
Open the housing to access the connections,
coding switches and LEDs. (
→
Chapter 3
"Installation" on page 3)
No.
Function
Description
1
CAN bus connection
2
CAN bus terminating resistor
3
Coding switch
1-7 CAN address:
for determining the CAN address in binary coding. The
address is the sum of the weights of the switches set to "ON".
Example:
to set address 40, slide switches 4 and 6 to ON. The sum of the
weights 8+32 is 40.
Coding switch
1
2
3
4
5
6
7
Weight at ON setting
1
2
4
8
16
32
64
8
Baud rate:
ON = 20kBit/s (fixed)
OFF= Automatic mode
4
Status LEDs
(from left to right)
1
Operating voltage and ready for use (flashes 1x per second)
2
No function
3
No function
4
No function
5
Receipt of a wireless telegram
6
CAN bus reception LED
7
CAN bus transmission LED
5
Mains power supply
230V
5
Technical data
Power supply
230V~, +10% / -15%, approx. 3VA
Display
Visible with housing open:
1 x LED, operation indicator
2 x LED, CAN bus data traffic
1 x LED, wireless reception
Communication
3-wire CAN bus interface
Dimensions
(WxHxD) 120 x 90 x 50mm
Fastening
Wall or ceiling installation
Ambient temperature
Operation: 0...+55°C, storage: -25…+70°C
Weight
About 350g
Reception antenna
Folds to positioning angles 0°, 45° and 90°
Technology
EnOcean, RCM
Transmission frequency
868.3MHz
Range
Building: approx. 30m, open area: approx. 300m
CE conformity
EU conformity as defined in
- 2014/53/EU (Radio Equipment Directive)
General approval for wireless operation applies for all EU countries and Switzerland.
RoHS II
Valid from
Version 1.70