CAN bus address setting 

To correctly register the FKV003 on the CAN bus, you must assign it a unique CAN bus address using 
a coding switch. This is a requirement for functioning communication with the master module. 
You can set CAN bus addresses 0–7 with the coding switch. You can thus connect 8 field modules to 
the CAN bus. 

 

Encoding switch 

 

Technical data 

Power supply 

230V~, +10% / -15%, max. 10VA 

Display 

1 x green LED, operating voltage 
2 x green LED, CAN bus data traffic (CAN Tx, CAN Rx) 
1 x red LED, flashing in case of fault 

Communication 

3-wire CAN bus interface, shielded, galvanically isolated, 
screw terminals 2.5mm / RJ45 socket (2x) 

Temperature sensor 

4 x TRK277 
(standard connection: supply air, return air, defrost limit, suction gas) 

Analogue input 

4...20mA or 0...10V=, output voltage 22V=, 
max. 22mA (humidity sensor, transmitter) 

Digital inputs 

24V=, +20% / -10%, approx. 5mA per input,  
1 x cold location off, 1 x 2nd setpoint, 1 x cold room door open 

Output relay 

1 x cooling, normally closed contact, 230V~, 4(2)A 
1 x fan, normally closed contact, 230V~, 4(2)A 
1 x defrosting, normally open contact, 230V~, 4(2)A 

Display / frame heating 

connection 

1 x socket for prefabricated cable to display DSP002, DSP100, DSP-
LCD, DSP-Booster or for controlling frame heating via ECA970 (1x) 

Analogue output 

1 x 0...10V=, non-isolated, max. load 10mA, for constant valves 

PWM / EEV output 

1 x 0...10V=, non-isolated, max. load 10mA, 
for control of electronic relays through ATV230 

Dimensions 

(WxHxD) 106 x 90 x 58mm (DIN 43880) 

Fastening 

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715) 

Ambient temperature 

Operation: 0...+55°C, storage: -25...+70°C 

Weight 

About 275g 

CE conformity 

  2014/30/EU (EMC Directive) 

  2014/35/EU (Low Voltage Directive)  

 

EAC conformity 

  TR CU 004/2011 

  TR CU 020/2011 

 

 

RoHS II 

Valid from 

Version 3.60 

 

 

Note! 

 Please observe the detailed descriptions in the chapters of the FRIGOLINK system manual. 

 