DOM-XP
4-channel weekly timer and telecontrol unit
Page 4 of 4
Subject to technical modifications
DOM-XP_V2.10_PI_2019-04_EN
Place the device with the upper guide edge on
the top-hat rail.
Then press the device gently downward until it
engages with the fastening safety catch on the
top-hat rail.
For wiring the data lines, we recommend using standard 2x2x0.8ø telephone cable with length up to
100m. The shielding must be grounded in the control cabinet. With cable lengths from 100m to 400m,
a shielded line with braided shield should be used.
For sensor extensions, it is recommended that sheathed cable be laid.
Cable length
Cross section
Up to 100m
0.75mm²
Up to 400m
1.5mm²
Technical data
Power supply
230V~, +10% / -15%, approx. 5VA
Digital inputs
4 x potential-free contact, for documentation only
(Internal power supply 12V=)
Output relay
4 x switching output, normally open contact, rated voltage
230V~, 4(2)A
Central unit
Single-chip microcomputer, data memory and quartz clock with
5000h power reserve
Monitoring system
Self-monitoring of data memory and microcomputer
Communication
3-wire CAN bus interface with integrated power supply,
galvanically isolated, service socket
Dimensions
(WxHxD) 106 x 90 x 58mm (DIN 43880)
Fastening
Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature
Operation: 0...+55°C, storage: -25…+70°C
Weight
About 450g
CE conformity
−
2014/30/EU (EMC Directive)
−
2014/35/EU (Low Voltage Directive)
EAC conformity
−
TR CU 004/2011
−
TR CU 020/2011
RoHS II
Valid from
Version 2.10