DOM-XP 

 
 

4-channel weekly timer and telecontrol unit 

 

Page 4 of 4 

Subject to technical modifications 

DOM-XP_V2.10_PI_2019-04_EN 

 

 

 
Place the device with the upper guide edge on 
the top-hat rail. 
Then press the device gently downward until it 
engages with the fastening safety catch on the 
top-hat rail. 

 
 
For wiring the data lines, we recommend using standard 2x2x0.8ø telephone cable with length up to 
100m. The shielding must be grounded in the control cabinet. With cable lengths from 100m to 400m, 
a shielded line with braided shield should be used. 
 
For sensor extensions, it is recommended that sheathed cable be laid. 
 

Cable length  

Cross section 

Up to 100m 

0.75mm² 

Up to 400m 

1.5mm² 

 
 

Technical data 

 

Power supply 

230V~, +10% / -15%, approx. 5VA 

Digital inputs 

4 x potential-free contact, for documentation only 
(Internal power supply 12V=) 

Output relay 

4 x switching output, normally open contact, rated voltage 
230V~, 4(2)A 

Central unit 

Single-chip microcomputer, data memory and quartz clock with 
5000h power reserve 

Monitoring system 

Self-monitoring of data memory and microcomputer 

Communication 

3-wire CAN bus interface with integrated power supply, 
galvanically isolated, service socket 

Dimensions 

(WxHxD) 106 x 90 x 58mm (DIN 43880) 

Fastening 

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715) 

Ambient temperature 

Operation: 0...+55°C, storage: -25…+70°C 

Weight 

About 450g 

CE conformity 

  2014/30/EU (EMC Directive) 

  2014/35/EU (Low Voltage Directive) 

 

EAC conformity 

  TR CU 004/2011 

  TR CU 020/2011 

 

 

RoHS II 

Valid from 

Version 2.10 

 

Содержание DOM-XP

Страница 1: ...angeover Delay times per channel Restoring of the logic switching state after a power failure Manual operation of the channels through digital inputs Documentation of the 4 digital inputs Simple parameter settings Display of relay states Parameter setting through plain text menu and direct operation Plug in screw terminals Clear text designation of switching outputs and digital inputs in FRIGODATA...

Страница 2: ...ntire plant when carrying out installation wiring or removal work Otherwise a mains voltage and or external voltage may still be present even if the control voltage is switched off Always remove both power plugs L and N Only qualified electricians are permitted to wire the device Use only the correct tools for all work Check all wiring after connection Take note of the maximum loads on all connect...

Страница 3: ...fire Switch off the power to the entire plant when carrying out installation wiring or removal work Otherwise a mains voltage and or external voltage may still be present even if the control voltage is switched off Always remove both power plugs L and N This device is designed for top hat rail installation The housing is of a standard size and is also suitable for installation in fuse boxes and di...

Страница 4: ...to 100m 0 75mm Up to 400m 1 5mm Technical data Power supply 230V 10 15 approx 5VA Digital inputs 4 x potential free contact for documentation only Internal power supply 12V Output relay 4 x switching output normally open contact rated voltage 230V 4 2 A Central unit Single chip microcomputer data memory and quartz clock with 5000h power reserve Monitoring system Self monitoring of data memory and ...

Отзывы: